Menu settings INSTALLER SETTINGS (contractors only) | 43
8 Menu settings INSTALLER SETTINGS
(contractors only)
Detailed instructions on navigating through the
menu structure, programming, deleting settings
and resetting to the factory settings are provided
in chapter 5.2 starting on page 21.
8.1 INSTALLER SETTINGS menu
summary and settings
The tables set out below provide:
An overview of the menu structure (column 1).
The menu depth is identified by various
shades of grey.
For example, in menu Solar sys parameters
submenus 1. Standard system and Solar
optimisation are on the same level.
An overview of the factory settings (column 2),
e.g. for the purposes of resetting individual
menu point to their factory settings.
An overview of the setting ranges of the
individual menu points (column 3).
Space for making a note of your personal
settings (column 4).
A way to locate detailed descriptions regarding
the individual menu points (column 5).
8.1.1 INSTALLER SETTINGS: System configuration
The INSTALLER SETTINGS menu is
intended only for contractors.
B To open INSTALLER SETTINGS:
press and hold for approx.
3 seconds.
menu
The menu points are only shown if
the system components are present
and/or active, and if no remote
control is accessing them. Some
menu points are not shown because
they are switched off by a setting for
another menu point.
B Always set or skip menu points in
order. In that way, subsequent
menu points will be
automatically adjusted or not
shown.
Menu structure
System configuration
Factory
setting
Setting range
Personal
setting
Description
from page
Start automatic system
configuration
No No | Yes
47
Domestic hot water
configuration
Combi boiler No | Combi boiler | Cyl conn to
boiler | Cyl on IPM ident.3 ... 10
DHW circulation pump No No | Present
CH system configuration Unmixed
without IPM
Unmixed without IPM | Unmixed
with IPM | Mixed
Remote control No No | FB 10 | FB 100
ISM 1 No No | Present
ISM 2 No No | Present