Operation Manual
6 720 645 349 (2010/09)
Menu settings INSTALLER SETTINGS (contractors only) | 45
8.1.4 INSTALLER SETTINGS: Solar sys parameters
8.1.5 INSTALLER SETTINGS: Fault history
Menu structure
Solar sys parameters
Factory
setting
Setting range
Personal
setting
Description
from page
1. Standard system – – –
52
SP: ON temperature
difference
8 K 3 K ... 20 K
(not lower than "SP: OFF
temperature difference" +1 K)
K
SP: OFF temperature
difference
4 K 2 K ... 19 K
(not higher than "SP: ON
temperature difference" – 1 K)
K
T2: Max. solar cylinder
temperature
60 °C 15 °C ... 95 °C °C
Maximum collector
temperature
130 °C 90 °C ... 135 °C °C
SP: Collector grp 1 pump
mode
Auto Auto | Manual On | Manual Off
PE: Therm disinfect pump mode Auto Auto | Manual On | Manual Off 53
Solar optimisation
53
Collector group 1 area 0.0 m
2
0.0 m
2
... 150.0 m
2
m
2
Collector group 1 type Flat plate
collector
Flat plate collector | Vac tube
collector
Climate zone 90 0 ... 255
Optimizing influence DHW 0 K 0 K (= function off) ... 20 K K
CH circuit optimizing
influence
0.0 K 0.0 K (= function off) ... 5.0 K K
Run solar system No No | Yes 55
Menu structure
Fault history
Factory
setting
Setting range
Personal
setting
Description
from page
01.01.2010
16:11
Fault EA
(example for last fault)
– – –
55
25.09.2010
18:45
FAULT 44 - IPM IDENT. 10
(up to a maximum of 19
previous faults)
– – –