50 | Menu settings INSTALLER SETTINGS (contractors only)
Sensor on FB10: The temperature sensor
fitted inside the remote control FB 10 is
used.
Menu: Heating parameters > Room temperature
offset
B Set the constant raising of the required room
temperature, e.g. to correct deviations due to
the system.
Menu: Heating parameters > Heating off until
lower level reached
B Select the cool-down phase:
No: Heating mode corresponds to the
heating curve.
Yes: Heating operation according to the
heating curve, however no heating
operation during the cool-down phase until
the current room temperature (e.g.
Comfort = 21.0 °C) reaches the required
room temperature of the next operating
mode down for the first time (e.g.
Economy with 15.0 °C). Afterwards,
heating commences in accordance with
the next operating mode down (e.g
Economy with 15.0 °C).
Menu: Heating parameters > Heating off at
outside temperature
B Set the outside temperature at which the
heating system should switch off:
10 °C ... 25 °C: Outside temperature at
which the heating system switches off.
99 °C: Function switched off, i.e. the
heating system can switch on at any
outside temperature.
Menu: Heating parameters > Freezing risk at
outside temperature
If the outside temperature exceeds the set
frost threshold temperature by 1 K ( °C) and
there is no heat demand, then the heating
circuit pump switches off.
If the outside temperature does not reach the
frost threshold temperature, then the heating
circuit pump switches on (system frost
protection).
B Set the frost threshold temperature at which
the heating system should switch on.
NOTICE: Heating water pipework
may freeze if the frost threshold is
set too low and there are long
periods of outside temperatures
below 0 °C.
B Factory setting of the frost
threshold (3 °C) must only be
adjusted to the system by a
heating contractor.
B Don’t set the frost threshold too
low.
Damage caused by the frost
threshold being set too low is
not covered by the warranty.