Operation Manual
6 720 645 349 (2010/09)
Menu settings INSTALLER SETTINGS (contractors only) | 51
Menu: Heating parameters > Calibrate room
temp sensor on FB10
Calibrate room temp sensor on FB10 only
appears if a remote control FB 10 is assigned.
Use this menu if you want to correct the
displayed room temperature.
B Position a precision instrument near FB 10.
The precision instrument must not transfer
any heat to the FB 10.
B Keep away from heat sources such as sunlight,
body heat, etc. for 1 hour.
B Adjust the displayed room temperature
correction value.
Menu: Heating parameters > Mixer running time
B Set the Mixer running time to the runtime of
the fitted mixer servomotor.
Menu: Heating parameters > Minimum outside
temperature
B Set the minimum outside design temperature
for the heating system (standard value
Æ table 9).
A low outside temperature results in a flat
heating curve.
Menu: Heating parameters > Building storage
capacity
B Set the factor for the thermal storage capacity
of the building.
– ≥ 50 %: Building of solid construction
(e.g. well insulated brick house).
– ≤ 50 %: Building of light construction
(e.g. wood or steel frame structure).
Menu: Heating parameters > Calibrate internal
room temp sensor
Calibrate internal room temp sensor only
appears if the controller is wall mounted.
Use this menu if you want to correct the
displayed room temperature.
B Position a precision instrument near FW 100.
The precision instrument must not transfer
any heat to the FW 100.
B Keep away from heat sources such as sunlight,
body heat, etc. for 1 hour.
B Adjust the displayed room temperature
correction value.
8.4 Configuring the solar thermal
system
Installer settings: Solar system config
For menu structure and setting ranges
Æ page 44.
Use this menu if you want to set the thermal
disinfection function for the solar thermal
system.
B In addition to the 1. Standard system set
option Solar sys option E Thermal
disinfection.
The pump (PE) is switched via menu Thermal
disinfection (Æ chapter 6.4.6 on page 37),
and the entire cylinder volume is heated to the
required thermal disinfection temperature.
Location
Minimum outside temperature
in °C
Brisbane 4
Canton 15
Chongqing 3
Hong Kong 6
Melbourne 0
Shanghai -1
Sydney 5
Tab. 9 Minimum outside temperatures for China
and Australia