Operation Manual

6 720 645 349 (2010/09)
Menu settings INSTALLER SETTINGS (contractors only) | 53
Menu: Solar sys parameters > 1. Standard
system > SP: Collector grp 1 pump mode
B Select the operating mode of the solar circuit
pump (SP):
Auto: Automatically controlled operation
according to the set parameters.
Manual On: Switches the pump
permanently on (e.g. for venting the solar
thermal system during commissioning).
Manual Off: Switches the pump
permanently off (e.g. for servicing the solar
thermal system without having to interrupt
heating operation).
8.5.2 Parameters for thermal disinfection
Menu: Solar sys parameters > PE: Therm
disinfect pump mode
B Select the operating mode for the pump (PE)
for thermal disinfection:
Auto: Automatically controlled operation
according to the set parameters.
Manual On: Switches the pump
permanently on (e.g. for function test
during commissioning).
Manual Off: Switches the pump
permanently off (e.g. for servicing the
pump without having to interrupt heating
operation).
8.5.3 Parameters for solar optimisation
Solar optimisation is performed automatically
according to the available solar output.
Calculation of the solar output requires a
specification of the installed collector area, the
collector type and the climate zone where the
system is installed.
Menu: Solar sys parameters > Solar
optimisation > Collector group 1 area
B Set the installed surface area of the collector
array.
Menu: Solar sys parameters > Solar
optimisation > Collector group 1 type
B Select the installed collector type for the
collector array.
Menu: Solar sys parameters > Solar
optimisation > Climate zone
B Set the value for the climate zone of the
installation location.
Collector
type
Gross area
per collector in m
2
FK 210 2.1
FK 240 2.4
FK 260 2.6
VK 180 1.8
FKT-1 2.4
FKC-1 2.4
FKB-1 2.4
Tab. 10 Gross collector areas