D9412GV2/D7412GV2 Release Notes for Version 7.05
© 2007 Bosch Security Systems, Inc. Page 3 F01U003637-02
• Minor corrections improve the user interface for
the following function list menus on the D1260
and D1260B Keypads:
Master Arm?
Master Arm Instant?
Perimeter Arm Delay?
Perimeter Arm Inst?
Disarm?
2.2 Version 7.03
• Changes allow Custom Functions to operate
correctly in the Function List when
CC# Menu
Lock
is set to Yes on the D1260 and D1260B
Keypads.
• Corrections disassociate the
L# Display Revision
authority level from the Service Menu on the
D1260 and D1260B Keypads.
• Corrections ensure that the authority level
permissions of each
L# Custom Function ###
are strictly associated with the correct Custom
Function number.
• If
Expanded Test Report
is set to Yes, Summary
Fire Supervision, Summary Fire Fault, Summary
Control Point Fault and Summary Point Device
are now included when a test report is sent using
COMMAND 41 or a sked.
• Corrections enhance the reliability and
performance of RPS network connection. These
corrections also decrease the delay in reporting a
break in the Ethernet connection to the control
panel’s Network Interface Module within the time
limits required by UL.
• For UL 1610 Line Security (formerly Grade AA)
Intrusion System installations and for UL 864
Commercial Fire installations, use the parameters
shown in Table 4 on page 3 when configuring the
Heartbeat Poll. For additional details, refer to
Programming Path Numbers and IP Addresses for
Enhanced Communications in the
D9412GV2/D7412GV2 Program Entry Guide
(P/N: F01U003636).
The recommended settings in Table 4
(Poll Rate of 75) enable the control panel
to annunciate locally, within 200 seconds,
any break in the network communication
path.
Table 4: Parameters for Heartbeat Poll
Configuration in Version 7.03
1
Number of
IP Paths
Poll Rate
(sec)
ACK Wait
Time (sec)
Number of
Retries
1 30 6 2 to 19
1 30 8 2 to 12
1 30 10 2 to 8
1 30 12 2 to 5
1 30 14 2 to 3
1 60 6 2 to 14
1 60 8 2 to 8
1 60 10 2 to 5
1 60 12 2
1 75
2
10
2
3
2
1 90 6 2 to 9
1 90 8 2 to 4
1 90 10 2
1 120 6 2 to 4
1 145 5 2
2 75
2
8
2
3
2
3 75
2
6
2
3
2
4 75
2
5
2
3
2
1
The parameters in this table are for Version 7.03 only.
2
Recommended settings for the corresponding number
of IP paths.
• Corrections allow the
Path # Retry Count
value
to be used as the number of retries instead of the
number of transmission attempts.
• When the control panel disconnects from an RPS
session using the network and the “Reset Panel”
checkbox is set, the control panel now logs a
Remote Reset event instead of a Reboot Event.
• Corrections now prevent the D9412GV2 and
D7412GV2 Control Panels from performing a
watchdog reset when an area is armed with more
than 75 manually bypassed points or has more
than 75 force bypassed points.
• Corrections now prevent the D9412GV2 and
D7412GV2 Control Panels from performing a
watchdog reset when an area with
A# Area Type
set to Shared is individually armed. Shared areas
should not be individually armed or disarmed.