Installation guide

D9412GV2/D7412GV2
D9412GV2/D7412GV2 Release Notes for Version 7.05
© 2007 Bosch Security Systems, Inc. Page 3 F01U003637-02
Minor corrections improve the user interface for
the following function list menus on the D1260
and D1260B Keypads:
Master Arm?
Master Arm Instant?
Perimeter Arm Delay?
Perimeter Arm Inst?
Disarm?
2.2 Version 7.03
Changes allow Custom Functions to operate
correctly in the Function List when
CC# Menu
Lock
is set to Yes on the D1260 and D1260B
Keypads.
Corrections disassociate the
L# Display Revision
authority level from the Service Menu on the
D1260 and D1260B Keypads.
Corrections ensure that the authority level
permissions of each
L# Custom Function ###
are strictly associated with the correct Custom
Function number.
If
Expanded Test Report
is set to Yes, Summary
Fire Supervision, Summary Fire Fault, Summary
Control Point Fault and Summary Point Device
are now included when a test report is sent using
COMMAND 41 or a sked.
Corrections enhance the reliability and
performance of RPS network connection. These
corrections also decrease the delay in reporting a
break in the Ethernet connection to the control
panel’s Network Interface Module within the time
limits required by UL.
For UL 1610 Line Security (formerly Grade AA)
Intrusion System installations and for UL 864
Commercial Fire installations, use the parameters
shown in Table 4 on page 3 when configuring the
Heartbeat Poll. For additional details, refer to
Programming Path Numbers and IP Addresses for
Enhanced Communications in the
D9412GV2/D7412GV2 Program Entry Guide
(P/N: F01U003636).
The recommended settings in Table 4
(Poll Rate of 75) enable the control panel
to annunciate locally, within 200 seconds,
any break in the network communication
path.
Table 4: Parameters for Heartbeat Poll
Configuration in Version 7.03
1
Number of
IP Paths
Poll Rate
(sec)
ACK Wait
Time (sec)
Number of
Retries
1 30 6 2 to 19
1 30 8 2 to 12
1 30 10 2 to 8
1 30 12 2 to 5
1 30 14 2 to 3
1 60 6 2 to 14
1 60 8 2 to 8
1 60 10 2 to 5
1 60 12 2
1 75
2
10
2
3
2
1 90 6 2 to 9
1 90 8 2 to 4
1 90 10 2
1 120 6 2 to 4
1 145 5 2
2 75
2
8
2
3
2
3 75
2
6
2
3
2
4 75
2
5
2
3
2
1
The parameters in this table are for Version 7.03 only.
2
Recommended settings for the corresponding number
of IP paths.
Corrections allow the
Path # Retry Count
value
to be used as the number of retries instead of the
number of transmission attempts.
When the control panel disconnects from an RPS
session using the network and the “Reset Panel”
checkbox is set, the control panel now logs a
Remote Reset event instead of a Reboot Event.
Corrections now prevent the D9412GV2 and
D7412GV2 Control Panels from performing a
watchdog reset when an area is armed with more
than 75 manually bypassed points or has more
than 75 force bypassed points.
Corrections now prevent the D9412GV2 and
D7412GV2 Control Panels from performing a
watchdog reset when an area with
A# Area Type
set to Shared is individually armed. Shared areas
should not be individually armed or disarmed.