Technical data

The control cabinet PC VPB 40.1
can be dam‐
aged if the power supply unit is switched off if
the total output power exceeds 110 W.
NOTICE
When maximum output currents are specified, please observe that the currents
are the maximum possible currents for the respective output voltage. However,
it is not possible to produce the maximum current from all output voltages at
the same time, as the maximum total output power (= max. 110 W) must not
be exceeded.
4.4 Ambient Conditions
In operation Storage / Transport
Max. surrounding air temperature +5 ℃ ... +45 °C -20 ℃ to +60 ℃
Max. temperature gradient Temporal temperature changes up to 3
per minute
Not defined
Relative humidity Climatic class 3K3 according to EN
60721,
non-condensing.
Climatic class 3K3 according to EN
60721,
non-condensing.
Air pressure Up to 2000 m above MSL according to
DIN 60204
Mechanical strength Max. vibration:
Frequency range:
10 to 150 Hz
Excursion: 0.075 mm for 10 ... 57 Hz
Acceleration: 1 g for 57 to 150 Hz
acc. to EN 60068-2-6
Max. shock:
15 g acc. to DIN IEC 68-2-27,
No breakdown of the function
Degree of pollution 2 2
Fig.4-4: Ambient conditions
4.5 Used Standards
The system components of the VPB 40.1 correspond to the following standards:
Standard
Meaning
EN 60 204-1 Electrical equipment of machines
EN 50 081-2 Generic standards - emission standard (industrial envi‐
ronments)
EN 50 082-2 Generic standards - noise immunity (industrial environ‐
ments)
EN 60 742 Transformer for 24 V power supply unit, protective sepa‐
ration
EN 60 950 Overvoltage category II
EN 61 131 24 V outputs requirements
EN 61 131-2 24 V current supply requirements
EN 418 Safety of machinery, emergency stop devices
DOK-SUPPL*-VPB*40.1***-PR02-EN-P
Rexroth IndraControl VPB 40.1 Control Cabinet PC
Bosch Rexroth AG 21/81
Technical Data