Specifications

Easy Series (ICP-EZM2) | Installer Guide | 7.0 Reference Materials
58 Bosch Security Systems, Inc. | 10/06 | F01U025147C
7.2 Power-limited Wire Routing
All wiring except primary AC power and standby battery is power-limited. Separate primary AC
power and standby battery wires from other wires by at least 6.4 mm (¼ in.), and secure to
enclosure to prevent movement.
Primary AC power and standby battery wiring cannot share the same conduit, conduit fittings, or
conduit knockouts with any other wiring.
6.4 mm
(¼ in.)
6.4 mm
(¼ in.)
1
2
3
1 - Primary 18 VAC power wiring.
2 - Standby battery wiring.
3 - Power-limited point and output wiring.