Install Instructions

Table Of Contents
52 | Commissioning
Greenstar FS
6 720 810 590 (2015/05)
Fig. 58
[1] Maximum Base Line Adjustment 186 °F (85 °C)
[2] Minimum Base Line Adjustment 50 °F (10 °C)
[3] Maximum Design Temperature Adjustment 186 °F (85 °C)
[4] Minimum Design Temperature Adjustment 86 °F (30 °C)
AT Outdoor temperature
VL Supply temperature
▶Turn the dial counter-clockwise until Maximum heating
supply temperature is highlighted.
▶Press the dial .
Turn the dial to set the desired value.
Press the dial to confirm the setting.
Press menu button to return to main display.
8.5.4 Adjusting warm weather shut down (WWSD)
▶To open INSTALLER SETTINGS: press and hold the menu button
for approx. 5 seconds.
System configuration will be highlighted.
Turn the dial one click counter-clockwise to highlight Heating
parameters.
▶Press the dial .
Heating circuit 1 will be highlighted.
▶Turn the dial counter-clockwise until Heating OFF at outdoor
temperature is highlighted.
Press the dial and the display will fl ash.
The default value is 68 °F (20 °C) and is adjustable from 50 °F (10 °C)
to 77 °F (25 °C). Turning above 77 °F (25 °C) will move it to 210 °F
(99 °C), which disables WWSD.
Press the dial to confirm the setting.
8.5.5 Resetting all settings (for installers only)
This function resets all settings on the MAIN MENU and the INSTALLER
SETTINGS to their factory settings. Following such a reset, you will
need to commission the system again!
If the default display is showing:
Simultaneously press and hold the menu button and the delete
button until a count down display appears.
Continue holding the menu button and the delete button
until the message appears that the reset is completed.
▶Press .
All settings have now been reset to their factory settings with the
exception of the date and time, which remain unchanged.
8.6 After commissioning
▶Check flue path for tightness.
Check gas supply dynamic pressure ( page 64).
Check that condensate is being discharged from the condensate
hose. If that is not the case, switch the appliance first OFF and then
ON again using the ON/OFF switch. That activates the trap filling
sequence ( page 59). Repeat the procedure several times until
condensate starts running out.
Complete commissioning report ( page 78).
8.7 KBR..-3A appliances (heating boilers) with DHW
tank: Setting the DHW temperature
Set the DHW temperature on the DHW thermostat .
The set DHW temperature flashes on the display for 30 seconds.
Fig. 59 Set the DHW temperature (heating boiler KBR..-3A)
ECO button
The default setting is DHW priority; the ECO button is not lit.
In order to switch between DHW tank priority and alternating
operation, press the ECO button.
DHW priority
First, the DHW tank is heated up to the set temperature. The
appliance then goes into heating mode. Therefore, it can happen that
space heating is interrupted for a while and the room temperature
6 720 806 992-07.1O
68 50 32 14 - 4
68
86
104
122
140
158
176
194
1
3
4
2
50
VL / °F
AT / °F
20 10 0 - 10 - 20
20
30
40
50
60
70
80
90
10
VL / °C
AT / °C
menu
menu
menu
menu
DHW thermostat Typical DHW temperatures
min approx. 59 °F (15 °C)
e approx. 131 °F (55 °C)
max approx. 158 °F (70 °C)
Table 17 Typical DHW temperatures for heating boiler KBR..-3A
WARNING: Danger of scalding!
In normal operation, it is recommended to limit the
DHW temperature to 122 °F (50 °C) to limit the risk
of scalding.
Install a tempering valve if running DHW
temperatures above 104 °F (40 °C).
Only use temperatures up to 158 °F (70 °C) for
thermal disinfection ( page 54).
If there is reason for concern for contamination from
bacteria such as Legionella, consider setting the DHW
thermostat to at least “e” (131 °F (55 °C)).
This setting ensures an economical and comfortable
DHW generation. Consult your local water department or
municipality for further information.
6 720 641 933-54.1O
max
1
2
34
5
6
reset
eco
max
1
2
3
4
e
6