54 | KBR..-3A appliances (heating boiler) with DHW tank: Thermal disinfection
Greenstar FS
6 720 810 590 (2015/05)
Fig. 64 Key pad lock
Unlocking the key pad:
Press the key pad lock button until the display shows only the supply
temperature.
9 KBR..-3A appliances (heating boiler) with DHW
tank: Thermal disinfection
Thermal disinfection covers the DHW system including the taps. For
solar DHW tanks, the solar portion of the tank is not covered.
Close all DHW taps.
Advise occupants of the risk of scalding if no tempering valve is
installed.
Set the time and DHW temperature accordingly on the heating
control with DHW program.
Set any DHW recirculation pump to continuous operation.
Turn DHW thermostat clockwise to max (approx. 158 °F (70 °C)).
Fig. 65 Thermal disinfection
Wait until the maximum temperature has been reached.
Open all DHW taps, from the nearest to the one furthest away, and
draw off hot water until it reaches a minimum of 158 °F (70 °C) at all
taps for at least 3 minutes.
Reset the DHW thermostat, DHW recirculation pump, and heating
control to standard operation.
WARNING: Risk of scalding!
Hot water can result in severe scalding.
Carry out thermal disinfection only outside the
normal hours of use, or install a tempering valve.
Thermal disinfection can also be carried out
automatically and on a regular basis; see operating
instructions for the heating control included in the scope
of delivery.