Install Instructions
Table Of Contents
- Table of Contents
- 1 Key to symbols and safety instructions
- 1.1 Key to symbols
- 1.2 General safety instructions
- 2 Scope of delivery
- 3 Information about the appliance
- 3.1 Proper use
- 3.2 Overview of boiler types
- 3.3 Rating plate
- 3.4 Appliance description
- 3.5 Accessories
- 3.6 Product dimensions and minimum clearances
- 3.7 Appliance layout heating boiler KBR..-3A
- 3.8 Appliance layout combi boiler KWB..-3A
- 3.9 Electrical wiring heating boiler KBR..-3A
- 3.10 Electrical wiring combi boiler KWB..-3A
- 3.11 Technical data heating boiler KBR 16-3
- 3.12 Technical data heating boiler KBR 21 -3
- 3.13 Technical data heating boiler KBR 28-3
- 3.14 Technical data heating boiler KBR 35-3
- 3.15 Technical data heating boiler KBR 42-3
- 3.16 Technical data combi boiler KWB 28-3
- 3.17 Technical data combi boiler KWB 35 - 3
- 3.18 Technical data combi boiler KWB 42 - 3
- 3.19 Condensate composition
- 4 Regulations
- 5 Common Applications of KBR boilers
- 6 Installation
- 6.1 Installation and operation
- 6.1.1 Notes on installation and operation
- Fill and make-up water for the heating system
- Recommended steps for commissioning a new or retrofit boiler installation
- Recirculation pump/DHW recirculation lines
- Open vented heating systems
- Gravity heating systems
- Galvanized radiators or pipes.
- Plastic pipe work
- Use of a room temperature control
- Primary-secondary piping or a Low Loss Header (LLH)
- Water Chemistry Guidelines
- Corrosion inhibitors
- Boiler sealer
- LPG
- 6.1.2 Other important information
- 6.1.1 Notes on installation and operation
- 6.2 Comparing the size of the integrated expansion vessel (KWB-3A boiler only)
- 6.3 KBR..-3A appliances (heating boilers): Selecting an expansion vessel
- 6.4 Selecting the installation location
- 6.5 Low Loss Header (LLH) utilization
- 6.6 Locating the appliance
- 6.7 Installing a low water cut off (LWCO)
- 6.8 Connecting flue gas accessories
- 6.9 Testing gas and water connections for leaks
- 6.1 Installation and operation
- 7 Making the electrical connections
- 8 Commissioning
- 8.1 Before operating the appliance
- 8.2 Switching the appliance ON/OFF
- 8.3 Setting up space heating
- 8.4 Programming the FW 200 heating control unit (optional accessory)
- 8.5 FW 200 outdoor reset heating control quick start (optional accessory)
- 8.6 After commissioning
- 8.7 KBR..-3A appliances (heating boilers) with DHW tank: Setting the DHW temperature
- 8.8 KWB..-3A appliances (combi boilers): Setting the DHW temperature
- 8.9 Setting manual summer mode
- 8.10 Setting frost protection
- 8.11 Activating the key pad lock
- 9 KBR..-3A appliances (heating boiler) with DHW tank: Thermal disinfection
- 10 Boiler circulator
- 11 Heatronic boiler control settings
- 11.1 Guideline to service functions
- 11.2 Overview of the service functions
- 11.3 Description of the service functions
- 11.3.1 First service level
- Service function 1.A: Maximum space heating output
- Service function 1.b: Maximum DHW output
- Service function 1.E: Pump mode for space heating operation
- Service function 1. F: Pump mode (only heating boiler KBR..-3A)
- Service function 2.A: Heating circuit pump lockout time (only heating boiler KBR..-3A)
- Service function 2.b: Maximum supply temperature
- Service function 2.C: Purging function
- Service function 2.d: Thermal disinfection (legionella protection)
- Service function 2.F: Operating mode
- Service function 3.A: Automatic anti-cycle function
- Service function 3.b: Set anti-cycle time
- Service function 3.C: Switching differential
- Service function 3.d: Minimum output (heating and DHW)
- Service function 3.E: Cycle time, keeping DHW hot (only combi boiler KWB..-3A)
- Service function 3.F: Constant DHW period (only combi boiler KWB..-3A)
- Service function 4.b: Maximum heat exchanger temperature (only combi boiler KWB..-3A)
- Service function 4.d: Audible fault warning tone
- Service function 4.E: Appliance type
- Service function 4.F: Condensate trap filling sequence
- Service function 5.A: Reset inspection interval
- Service function 5.b: Fan post purge time
- Service function 5.E: Functionality of black plug in boiler junction box
- Service function 5.F: Set inspection interval
- Service function 6.A: Display the latest fault code
- Service function 6.b: Room temperature control, current voltage, terminal 2
- Service function 6.C: Supply temperature required by weather compensation control
- Service function 6.d: Current DHW turbine flow rate (only combi boiler KWB..-3A)
- Service function 7.A: Indicator lamp for burner operation / faults
- Service function 7.b: 3-way valve in center position
- Service function 7.d: Connecting an external supply or low-loss header temperature sensor
- Service function 7.E: Building drying function
- Service function 0.A: Do not use this setting!
- Service function 0.d: Altitude adjustment
- Service function 0.E: Metric or US customary units
- 11.3.2 Second service level
- Service function 8.A: Software version
- Service function 8.b: Code plug number
- Service function 8.C: GFA Gas burner control unit status
- Service function 8.d: GFA Gas burner control unit fault
- Service function 8.E: Restore boiler to factory settings
- Service function 8.F: Permanent ignition
- Service function 9.A: Constant mode
- Service function 9.b: Current fan speed
- Service function 9.C: Current boiler output
- Service function 9.d: Set fan start speed
- Service function 9.E: Turbine signal delay (only combi boiler KWB..-3A)
- Service function 9.F: Heating zone pump post purge
- Service function A.b: Display DHW temperature
- Service function A.C: Display DHW tank temperature
- Service function b.F: Solar DHW backup heating delay (only combi boiler KWB..-3A)
- Service function C.d: Display current heat demand
- 11.3.1 First service level
- 12 Gas type conversion
- 13 Flue gas test
- 14 Environmental responsibility/disposal
- 15 Inspection and maintenance
- Heat exchanger
- Heatronic boiler control
- Notes on installation and operation
- After the inspection/maintenance
- 15.1 Description of various steps
- 15.1.1 Calling up the latest fault (service function 6.A)
- 15.1.2 Fresh water filter (only combi boiler KWB..-3A)
- 15.1.3 Plate type heat exchanger (only combi boiler KWB..-3A)
- 15.1.4 Checking the electrodes
- 15.1.5 Burner servicing
- 15.1.6 Heat exchanger block inspection and cleaning
- 15.1.7 Condensate trap cleaning
- 15.1.8 Checking the mixer diaphragm
- 15.1.9 Expansion vessel
- 15.1.10 Setting the boiler water pressure
- 15.1.11 Testing system water quality
- 15.1.12 Inspecting electrical wiring
- 15.2 Checklist for annual inspection and maintenance
- 16 Readings on the display
- 17 Faults
- 18 Commissioning log for the appliance
- 19 Spare parts
- Index
62 | Gas type conversion
Greenstar FS
6 720 810 590 (2015/05)
12 Gas type conversion
The gas-air ratio must always be set on the basis of a CO
2
or O
2
reading taken at maximum nominal output and minimum nominal
output using an electronic flue gas analyzer.
Adjustment to different flue systems using throttle discs or baffles is not
necessary.
NG
• Appliances are set at the factory to Wobbe index 1,333 BTU/ft
3
(49.6 MJ/m
3
) at 60 °F (15 °C), 30" Hg (1016 hPa) and 7.0" W.C.
(17.4 mbar) gas supply pressure and sealed.
12.1 Converting to a different gas type
A gas conversion kit is included in the scope of delivery.
▶ Swing the Heatronic to the left.
▶ Check the number on the code plug from the gas conversion kit
(Code plug number table 34, page 77).
▶ Replace the code plug in the Heatronic with the code plug from the
gas conversion kit.
Fig. 69 Replacing the code plug
▶ Affix the provided LP gas label from the gas conversion kit onto the
original NG gas type label. It is important to cover the original gas type
information located at the bottom of the original gas type label.
Fig. 70 Affixing the gas type label
[1] Rating plate
[2] Model name and serial number
[3] Technical data
12.2 Installation location higher than 2,000 feet (610 m)
above sea level
Input and output rates are reduced at higher altitudes due to thin air with
reduced oxygen levels.
KBR42-3A... and KWB42-3A... appliances are derated at 3 % per
1000 feet (305 m).
KBR30-3A and KWB30-3A appliances offer altitude adjustment which
compensates for the effects of thin air, and are therefore NOT derated
up to 6000 feet (1829 m). Above 6000 feet (1829 m) a rate of 3% per
1000 feet (305 m) applies.
▶ Correction of the fan speed curve of the burner:
Use service function 0.d to adjust the elevation setting ( page 60).
DANGER: Personal injury and property damage
▶ This conversion shall only be performed by a trained
and certified installer in accordance with the
manufacturer‘s instructions and all applicable codes
and requirements of the authority having
jurisdiction.
▶ If the information in these instructions is not followed
exactly, or the installation, adjustment, modification,
operation or maintenance is carried out by an
unqualified person, a fire, explosion or generation of
large amounts of carbon monoxide may result
causing property damage, personal injury or loss of
life.
▶ Before carrying out electrical work: Disconnect the
installation from the power supply at the emergency
shutoff switch or by disengaging the heating system
circuit breaker. Take measures to prevent accidental
re-connection.
▶ The installer is responsible for the proper conversion
of this appliance.
▶ The conversion is not complete until the operation of
the converted appliance is checked as specified in
these instructions.
DANGER: Explosion!
▶ Close the gas cock prior to working on the gas train.
▶ Check for gas leaks after carrying out work on the gas
train.
6 720 641 933-57.1O
Always adjust the gas-air ratio (CO
2
or O
2
),
▶ Section 12.3) after converting to a different gas type
and measure the CO content of the flue gas
( Section 13).
The Bosch Greenstar boiler is factory set for installation
below 2000 feet (610 m) above sea level.
6720810590-11.1Wo
2
1
3