68 | Inspection and maintenance
Greenstar FS
6 720 810 590 (2015/05)
Remove the burner and clean the components.
Fig. 86 Burner
Reinstall the burner in reverse order, including a new gasket.
Adjust the gas-air ratio ( page 63).
15.1.6 Heat exchanger block inspection and cleaning
Remove the inspection cover ( page 8) and any sheet metal insert
below, if installed.
Determine degree of soiling of the heat exchanger through visual
inspection.
If mechanical cleaning is required:
For cleaning the heat exchanger, use Bosch main heat exchanger
gaskets, the heat exchanger brush and the heat exchanger cleaning
blade which are available as spare parts.
Remove the condensate trap (steps 1 and 2) and place a suitable
container underneath.
Fig. 87 Removing the condensate trap
With the cleaning blade, clean the heat exchanger block from the
bottom to the top.
Fig. 88 Cleaning the heat exchanger with the cleaning blade
NOTICE: Damage to the coating of the heat exchanger.
Cleaning of the heat exchanger should not be
necessary until five years after the initial
commissioning.
Only use a Bosch cleaning blade and Bosch cleaning
brush ( page 69).
Only clean heat exchanger in case if soiling is clearly
visible.
7 181 465 330-08.2R
6 720 641 933-93.1o
1
2
6 720 641 933-71.1O