Technical data

WARNING
The enabling switch is only suitable as a protective function if the person
actuating the enabling switch identifies potential hazards to people in
time and immediately takes measures to prevent such hazards!
A
reduced velocity of travel may be required as additional measure. The per‐
mitted velocity must be determined on the basis of a risk evaluation.
No commands that result in hazardous states may be triggered using only a
single enabling switch. A second starting command is required for this (key on
manual operating device).
Only the person actuating the enabling switch may remain in the area of risk.
STOP Push Button
The IndraControl VAC 30.2 is equipped with an automatic STOP circuit jumper.
This allows the operator to connect or disconnect the hand-held terminal In‐
draControl VCH 08.1 via the IndraControl VAC 30.1 connection module without
causing the unintended stopping of the system.
Before starting up the IndraControl VCH 08.1 it must be ensured
that the STOP push button is not depressed. The connection of a
IndraControl
VCH 08.1 with a depressed STOP push button would
shut down the system.
Functionality of the STOP Circuit Jumper
Fig.6-7: STOP circuit jumper
If the hand-held terminal IndraControl VCH 08.1 is not plugged in, the contacts
K1.1 and K1.2 of relay K1 in the IndraControl VAC 30.1 connection module
32/80 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl VCH 08.1 | Project Planning Manual
Display and Operating Components