Instruction manual

42
Technical information
Technical information
Greenstore System, Brine/Water heat pump 6 7 9 11
Emitted/ Supplied output at 0/45°C
1
kW 5.19/1.80 6.55/2.20 8.20/2.67 9.63/2.92
COP
1
2.89 2.97 3.06 3.29
Minimum fl ow heating side l/s 0.14 0.18 0.22 0.26
Nominal fl ow heating side l/s 0.20 0.25 0.31 0.38
Maximum pressure available heating side (at nominal fl ow) kPa 36 36 34 32
Nominal fl ow of antifreeze mixture to the collector hose l/s 0.30 0.38 0.46 0.57
Maximum pressure available to collector hose (at nominal fl ow) kPa 49 45 44 80
Type of antifreeze
Bioethanol-water or
Propylene/ethylene glycol / -water
Freeze protection temperature °C -15
Maximum pressure heating side of heat pump bars 2.5
Maximum pressure on collector hose side bars 4
Maximum outgoing temperature to the heating system °C 65
Maximum return temperature from heating system °C 57
Working temperatures on collector hose side °C -5 to +20
Integrated collector hose and heating system pump Yes
Power supply 230V 1N~ 50Hz
Additional heat settings kW 3,0 / 6,0 / 9,0
The recommended type of fuse according to electrical output
2
6 kW electric heater
9 kW electric heater
AaM 40 40 50 50
AaM 50 63 63 63
Starting current, soft start
A 22.9 23.8 30.9 34.6
Compressor Scroll
Type R-407C HFC refrigerant kg 1.35 1,4 1.5 1.9
Connection for heat fl uid out/in mm Cu 22
Out/in collector hose connection mm Cu 28
Dimensions of heat pump (LxDxH) mm 600x600x1520
Weight of heat pump kg 149 153 155 164
Control unit Reg 637W
Ambient temperature (indoor use) °C +10 to +30
Maximum relative humidity rH 60%
Sound power level
3
dB(A) 47.2 50.1 51.9 48.3
Sound pressure level
4
dB(A) 34.5 37.4 39.2 35.6
1
Data at 0/45°C according to the European standard EN 14511. Data applies to a new unit with clean heat exchangers.
2
aM type fuse, D characteristic MCB.
3
Measurement according to EN ISO 3743-2.
4
Calculated values at 1 m distance according to EN ISO 11203.