52 | Commissioning
Greenstar6 720 806 992 (2013/09)
8.2 Switching the appliance ON/OFF
Startup
Switch the appliance ON using the ON/OFF switch.
The display indicates the supply temperature of the hot water in °F. If
necessary, convert to °C ( Service function 0.E: Metric or US
customary units, page 63)
Fig. 60 Switching the appliance ON/OFF
Open the automatic vent [9] (only combi boiler
ZWB..-3A) and close it again when the purging sequence has finished
( page 51).
Shutdown
Switch appliance OFF using the ON/OFF switch.
The display goes out.
If the appliance is taken out of service for a longer period: Observe
frost protection ( Section 8.10).
8.3 Setting up space heating
Set the maximum supply temperature based on the structure's heat loss
on design day.
In order to set the maximum supply temperature, turn the boiler high
limit dial .
Fig. 61 Switch on heat
If the burner is operating, the burner operation indicator lamp is
illuminated.
8.4 Programming the FW 200 heating control unit
Fig. 62 FW 200 heating control with front flap closed / flap opened
When the appliance is switched ON for the first time, it
performs a once-only purging sequence. This involves
the heating zone pump switching on and off at intervals
(for approx. 4 minutes).
The display shows in alternation with the supply
temperature.
If the display shows in alternation with the supply
temperature, the trap filling function is active
( page 62).
Boiler high limit
dial
Typical supply
temperatures
Sample application
1 approx. 95 °F
(35 °C)
Frost protection
2 approx. 109 °F
(43 °C)
3 approx. 122 °F
(50 °C)
Radiant floor heating system
4 approx. 140 °F
(60 °C)
Panel radiator system
5 approx. 153 °F
(67 °C)
Cast iron radiator system
6 approx. 167 °F
(75 °C)
max approx. 194 °F
(90 °C)
Baseboard and convector
system
Table 25 Typical supply temperatures
max
1
2
3
4
5
6
6 720 613 896-05.1O
With radiant floor heating, limit the maximum
permissible supply temperature as recommended by the
manufacturer.
Observe the operating instructions for the heating
control included in the scope of delivery. There you can
read:
How to set the operating mode and the heating curve
for outdoor reset controls
How to adjust the room temperature
How to heat economically and comfortably
How the control can be mounted in the boiler or in the
living space
eco
reset
6 720 641 933-53.2O
max
1
2
3
4
5
6
max
1
2
3
4
e
6
min
6 720 643 256-01.1O
3
3
4
1
menu info
1
2
3
5
6
7
8
4
9
12
h
15
18
2124
h
3
6