Faults | 77
6 720 806 992 (2013/09)Greenstar
17.2 Faults that are shown on the display
Display Description Elimination
A7 DHW temperature sensor defective. Check temperature sensor and leads for interruptions or shorts, and replace if
defective.
Insert code plug correctly; replace if defective.
A8 Communication fault. Check BUS communications wiring, replace if defective.
Check control, replace if defective.
Ad DHW tank temperature not detected.
The DHW tank temperature sensor was recognized
before the connection was lost.
Check DHW tank temperature sensor and connecting lead, replace if defective.
Reset the boiler to the factory default settings ( service function 8.E), reset the
IPM 2 (if installed) to the factory default settings and carry out the automatic
system configuration.
b1 Code plug not detected. Insert code plug correctly; replace if defective.
b2/b3/b4/
b5/b6
Internal data error. Reset boiler to factory default setting ( service function 8.E).
b7 Fault in the burner controls. Reset boiler to factory to default setting ( service function 8.E).
C6 Fan not running. Check fan leads and fan, replace if defective.
CC Outdoor temperature sensor not recognized. Check outdoor temperature sensor and leads for interruptions, replace if
defective.
Verify the outdoor temperature sensor is connected to terminals A and F.
d3 Temperature high limit defective.
External guard has tripped.
Temperature limiter locked out.
Check temperature sensor and leads for interruptions or shorts, and replace if
defective.
Temperature guard TB1 has tripped. Check if jumper across 8-9 or PR-P0 is
missing.
Reset external temperature limiter (if installed).Reset LWCO (if installed).
d5 External supply temperature sensor defective
(low-loss header).
The external supply temperature sensor was
recognized on the BUS and then reconnected to
the appropriate terminal.
Check temperature sensor and leads for interruptions or shorts, and replace if
defective.
Check whether only one temperature sensor is connected; otherwise remove
second temperature sensor.
Reset the boiler to the factory default settings ( service function 8.E), reset the
IPM 2 (if installed) to the factory default settings and carry out the automatic
system configuration.
E2 Supply temperature sensor defective. Check temperature sensor and leads for interruptions or shorts, and replace if
defective.
E3 Additional supply temperature sensor defective. Check temperature sensor and leads for interruptions or shorts, and replace if
defective.
E9 Heat exchanger safety high limit or flue gas
temperature limiter has tripped.
Check flue gas safety high limit and leads for interruptions or shorts, and replace
if defective.
Check heat exchanger safety high limit and leads for interruptions or shorts, and
replace if defective.
Check the operating pressure.
Check temperature limit; replace if defective.
Check pump capacitor; replace pump if defective.
Check PCB fuse, replace if blown (6.3 A fuse according to IEC default).
Purge the appliance
Check heat exchanger on the DHW side; replace if clogged.
Table 38 Faults shown on the display