User Guide

Thermal disinfection | 23
6 720 806 993 (2013/03)
Greenstar
Thermal disinfection covers the DHW system including the taps. For solar DHW
tanks, the solar portion of the tank is not covered.
Performing a manual disinfection of the DHW tank and system
Close all DHW taps.
Advise occupants of the risk of scalding if no tempering valve is installed.
Set the time and DHW temperature accordingly on the heating control unit with
DHW program.
Set any DHW recirculation pump to continuous operation.
Turn DHW thermostat clockwise to max (approx. 158 °F (70 °C)).
Fig. 13
Thermal disinfection can also be carried out automatically and on a
regular basis; see operating instructions for the heating control unit
included in the scope of delivery.
DANGER: Risk of scalding!
Hot water can result in severe scalding.
Carry out thermal disinfection only outside the normal hours of use.
The water in the tank will take a while to cool down to the set DHW
temperature as a result of heat loss. Be aware that, after thermal
disinfection, the DHW may be hotter than the set temperature.
If the thermal disinfection feature is activated have a DHW
tempering valve installed.
6 720 614 156-16.1O
max
1
2
34
5
6
reset
eco
max
1
2
3
4
e
6