38 | Installation
Greenstar6 720 806 992 (2013/09)
In case of open venting:
Use basket on the air intake.
In case of concentric venting system:
Fig. 28 Horizontal venting system (telescopic concentric vent kit)
[1] Intake
[2] Exhaust
L 2 feet to 3 feet (610 mm to 915 mm)
Install the concentric vent adaptor with the screws enclosed.
Fig. 29 Installing the concentric vent adaptor
[1] Concentric vent adaptor
[2] Screws
[3] Combustion air test port
[4] Flue gas test port
6.8.1 Installation of the exhaust and air intake system
To avoid premature wear of the gaskets DO NOT use
lubricants.
As an alternative to twin pipe venting, a bespoke
telescopic concentric vent kit can be obtained as an
accessory from Bosch Thermotechnology for a
horizontal direct vent wall termination. This vent system
can be used for vent lengths of 2 feet to 3 feet (610 mm
to 915 mm).
For more details on connecting the flue system, refer to
the installation instructions for the flue kit.
6 720 806 992-02.1O
L
1
2
6 720 806992-01.1O
1
2
34
NOTICE:
Vent connectors serving appliances vented by natural
draft shall not be connected to any portion of
mechanical draft systems operating under positive
pressure.
NOTICE: Burner damage!
Avoid drawing in combustion air excessively loaded
with dust or airborne particles.
DANGER:
Ensure that the flue pipes and seals are not damaged.
Use only sealing compounds (primer and glue)
approved with the vent material.
Never install a barometric nor a thermally controlled
vent damper with this boiler.
Connect only one boiler to each flue system or
chimney flue.
Do not route the flue system piping through or inside
another duct that is used for exhausting air or other
flue gases.
The condensate trap must be primed at all times.
Failure to do so may allow combustion gases to
escape into boiler room.
External insulation on plastic vent pipe is prohibited.
Consult local and state codes pertaining to special
building code and fire department requirements. Adhere
to national code requirements.
Observe the listed maximum lengths of vent system,
which are boiler model dependent ( chapter 6.8.3).