Table of contents Table of contents 1 General information................................................................................................................................. 1.1 Further information........................................................................................................................... 1.2 Notational conventions.................................................................................................................... 1.3 Symbols and signal words.....
PSA-321 power distributor
General information 1 General information This user manual contains important information on the safe operation of the device. Read and follow all safety notes and all instructions. Save this manual for future reference. Make sure that it is available to all persons using this device. If you sell the device to another user, be sure that they also receive this manual. Our products and user manuals are subject to a process of continuous development.
General information 1.1 Further information On our website (www.thomann.de) you will find lots of further information and details on the following points: Download This manual is also available as PDF file for you to download. Keyword search Use the search function in the electronic version to find the topics of interest for you quickly. Online guides Our online guides provide detailed information on technical basics and terms.
General information 1.2 Notational conventions This manual uses the following notational conventions: Letterings The letterings for connectors and controls are marked by square brackets and italics. Examples: [VOLUME] control, [Mono] button. 1.3 Symbols and signal words In this section you will find an overview of the meaning of symbols and signal words that are used in this manual.
General information Signal word Meaning DANGER! This combination of symbol and signal word indicates an immediate dangerous situation that will result in death or serious injury if it is not avoided. NOTICE! This combination of symbol and signal word indicates a pos‐ sible dangerous situation that can result in material and environmental damage if it is not avoided. Warning signs Type of danger Warning – high-voltage. Warning – danger zone.
Safety instructions 2 Safety instructions Intended use This device is used to distribute electrical power to multiple connected loads. The device is designed for professional use only and is not suitable for use in households. Use the device only as described in this user manual. Any other use or use under other operating conditions is considered to be improper and may result in personal injury or property damage. No liability will be assumed for damages resulting from improper use.
Safety instructions Safety DANGER! Danger for children Ensure that plastic bags, packaging, etc. are disposed of properly and are not within reach of babies and young children. Choking hazard! Ensure that children do not detach any small parts (e.g. knobs or the like) from the unit. They could swallow the pieces and choke! Never let children unattended use electrical devices. DANGER! Electric shock caused by high voltages inside Within the device there are areas where high voltages may be present.
Safety instructions DANGER! Electric shock caused by short circuit Always use a properly insulated CEE cable to connect the unit to the 400 V mains grid. Do not modify the CEE cable or the CEE plug. Failure to comply may result in electric shock and risk of fire and loss of life. If in doubt, seek advice from a regis‐ tered electrician. NOTICE! Risk of fire Do not block areas of ventilation. Do not install the device near any direct heat source. Keep the device away from naked flames.
Safety instructions NOTICE! Operating conditions This device has been designed for indoor use only. To prevent damage, never expose the device to any liquid or moisture. Avoid direct sunlight, heavy dirt, and strong vibrations. Only operate the device within the ambient conditions specified in the chapter ‘Technical specifications’ of this user manual.
Safety instructions NOTICE! Power supply Before connecting the device, ensure that the input voltage (AC outlet) matches the voltage rating of the device and that the AC outlet is protected by a residual current circuit breaker. Failure to do so could result in damage to the device and possibly injure the user. Unplug the device before electrical storms occur and when it is unused for long periods of time to reduce the risk of electric shock or fire.
Features 3 Features n 3-phase power distributor to 6 × 16 A n Digital voltage (‘V’) and current (‘A’) display for each output n Input – Cable with CEE plug for 3 × 32 A (400 V) n Outputs – 6 × EU safety sockets with hinged lid for each 16 A (250 V) – 1 × 5-pin CEE chassis socket with hinged lid for 32 A (400 V) n Circuit breaker with trigger switch for each output n Four-pole residual current device (RCD, residual current circuit breaker) for the input n Robust steel sheet housing with black epoxy powder
Installation and starting up 4 Installation and starting up Unpack and check carefully there is no transportation damage before using the unit. Keep the equipment packaging. To fully protect the product against vibration, dust and moisture during transportation or storage use the original packaging or your own packaging material suitable for transport or storage, respectively. Create all connections while the device is off. Use power supply cables with earthed earthing pin plug or 5-pin CEE-plug only.
Connections and controls 5 Connections and controls Front panel 16 PSA-321 power distributor
Connections and controls 1 Residual current device (RCD). This protective device, also known as ‘Fehlerstrom-Schutzschalter’ or ‘FI-Schalter’ in German-speaking countries, is used for personal protection. As soon as it detects differential current / fault current, it automatically disconnects the device from the mains. [T]: Button for manual triggering the residual current device (RCD).
Connections and controls Rear panel 18 PSA-321 power distributor
Connections and controls 4 5-pin CEE chassis socket with hinged lid. 5 6 × EU safety socket with hinged lid for the six outputs. 6 Power cable with CEE plug.
Technical specifications 6 Technical specifications Input connections Power supply Output connections 3 × CEE plug, 3 × 32 A 6 × EU safety socket 230 V, 16 A 1 × CEE chassis socket 32 A, three-phase Safety Residual current device (RCD) / input 40 A, 4-pin, 0.03 A Line circuit breaker / outputs: 6 × 16 A Supply voltage 400 V Degree of protection IP44 Mounting options Thread Installation 19", 3 RU Dimensions (W × H × D) 482 mm × 133 mm (3 RU) × 198 mm Weight 7.
Technical specifications Ambient conditions Temperature range 0 °C…40 °C Relative humidity 50 %, non-condensing Further information Power handling 32 A Residual current circuit breaker Yes Fuses 6 × automatic fuse 16 A C Switch No Rack format Yes PSA-321 power distributor 21
Protecting the environment 7 Protecting the environment Disposal of the packaging mate‐ rial For the transport and protective packaging, environmentally friendly materials have been chosen that can be supplied to normal recycling. Ensure that plastic bags, packaging, etc. are properly disposed of. Do not just dispose of these materials with your normal household waste, but make sure that they are collected for recycling. Please follow the notes and markings on the packaging.