Installing Vent Components
Begin the vent system installation by installing the rst Duravent component to the starting collar, 24 inch (60.10 cm) minimum straight
pipe on the top of the appliance, then the remaining pipe length and the horizontal or vertical termination kit.
NOTE: All outer connection joints must be sealed with aluminum tape, screws or silicone sealant rated above 300°F/149°C. The
inner ue joints do not require any sealant.
Duravent vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto
the appliance collar or previously installed component end with four (4) equally spaced indented sections. When the internal beads of each
starting outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.
Continue adding components per the pre-planned vent system conguration. Be certain that each succeeding vent component is securely
tted and locked into the preceding component in the vent system.
Special Venting Components (Duravent)
See Empire Comfort Systems Retail Price List for 4 x 6-5/8 inch Duravent part numbers and pricing.
▲
▼
◄
◄
◄
◄
▼
▲
▲
▲
▲
PIPE LENGTH
WALL STRAP
90° ELBOW
WALL THIMBLE
CEILING FIRESTOP
90° ELBOW OR
45° ELBOW
HORIZONTAL TERMINATION
(MAXIMUM OF TWO 90° ELBOWS)
VERTICAL TERMINATION
(MAXIMUM OF
THREE 90° ELBOWS)
STORM COLLAR
ROOF FLASHING