Owner`s manual

29843-2-0612 Page 29
VERTICAL TERMINATION
Vertical Through the Roof Applications
Your Gas Fireplace has been approved for:
a) Vertical installations up to 40 ft. (12.19 m) in height.
b) Two sets of 45 degree elbow offsets within these vertical
installations. From 0 to a maximum of 8 ft. a vent pipe can be
used between elbows. See Figure 43.
c) Wall straps must be used to support offset pipe every 4 ft.
(1.22 m).
This application will require that you rst determine the roof pitch
and use the appropriate venting components.
45°
45°
40’
(12.19M)
MAXIMUM
8’
(2.44M)
MAXIMUM
8’
(2.44M)
MAXIMUM
TYPICAL ROOF
SUPPORT
TYPICAL JOIST
SUPPORT
Figure 43
Installing the Vent System in a Chase
A chase is a vertical box-like structure built to enclose the gas
appliance and/or its vent system. Vertical vent runs on the outside of
a building may be, but are not required to be installed inside a chase.
CAUTION: Treatment of restop spacers and construction of
the chase may vary with the type of building. These instructions
are not substitutes for the requirements of local building codes.
Therefore, your local building codes must be checked to determine
the requirements for these steps.
NOTE: When installing this vent system in a chase, it is always good
building practice to insulate the chase as you would the outside
walls of your home. This is especially important for cold climate
installations. Upon completion of building your chase framing,
install the vent system by following the instructions in this manual.
Remember to build the chase large enough so that minimum
clearance of combustible materials (including insulation) to the vent
system are maintained.
Reassembly and Resealing Vent Pipe System
Attach vent pipe to inlet and outlet vent adaptor on replace, replace
horizontal and vertical pipe lengths, elbows and horizontal or vertical
termination kit.
All vent system components lock into place by sliding the concentric
pipe section with four (4) equally spaced interior beads onto the
appliance collar or previously installed component end with four
(4) equally spaced indented sections. When the internal beads of
each starting outer pipe line up, rotate pipe section clockwise 90°
(approximately 3 inches). The vent pipe is now locked together.
Continue replacing components per the vent system conguration.
Be certain that each succeeding vent component is securely tted
and locked into the preceding component in the vent system.
FEMALE
LOCKING
LUG
MALE
LOCKING
LUG
Figure 42