Owner`s manual
29843-2-0612Page 8
Mantel Chart
IMPORTANT NOTE:
NO COMBUSTIBLES MAYBE
PLACED IN THE AREA
BETWEEN THE TOPOF THE
FIREPLACE AND THE MANTEL
12”
(305)
13 ½”
(343)
14 ½” (368)
15 ½” (394)
16 ½” (419)
17 ½” (444)
18 ½” (469)
19 ½” (495)
20 ½” (521)
13”(330)
14”(356)
15”(381)
16”(406)
17”(431)
18”(457)
19”(482)
20”
(508)
21 1/2” (546)
Figure 4
Ceiling Height and Side Wall Clearances
Minimum ceiling height is 46" (116.8cm)
Clearance from side of replace to adjacent sidewall is 2" (51mm).
Note: Some decorative fronts require more than 2" clearance due
to front size.
▲
►
▼
◄
21-1/2”
()546mm
MINIMUM
2”
()51mm
Figure 5
CLEARANCES
Clearance to Combustibles - Shown in inches (metric)
Back 1-1/4 (32mm)
Side 3-1/8 (79mm)
Floor 0 (0mm)
Top Stand-off 12 (305mm)
Top Framing Edge 12 (305mm)
Minimum Height Floor To Ceiling 45-3/4 (116.2cm)
IN THIS AREA
HEADER RECOMMENDATION:
USE DOUBLE
HEADER OR PLACE
HEADER VERTICALLY
SEE MANTEL
CHART FOR
MAXIMUM MANTEL DEPTH
AND HEIGHT
57-7/16”
(145.0cm)
STANDOFF 12” (305mm)
HEIGHT ABOUT
TOP OF FIREPLACE
NON-COMBUSTIBLE
FINISHED WALL
FIRST 13-1/2” (343mm)
1-1/4” (32mm)
►
▲
▼
◄
▲
▲
▼
▼
▲
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the replace. The ow of heat can
ignite combustibles.
ONLY NON-COMBUSTIBLE MATERIALS
ALLOWED OVER THE FIREPLACE FACE
ON EACH SIDE
3-1/8” (79mm)
3-1/8” (79mm)
1-1/4” (3mm)
Figure 3