GAS SUPPLY
The gas pipeline can be brought in through the left side of the
appliance.ConsultthecurrentNationalFuelGasCode,ANSIZ223.1
CAN/CGA-B149(.1or.2)installationcode.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat. L.P. Nat. L.P.
0-10ft
0-3m
1/2in.
12.7mm
3/8in.
9.5mm
1/2in.
12.7mm
3/8in.
9.5mm
11-40ft
4-12m
1/2in.
12.7mm
1/2in.
12.7mm
5/8in.
15.9mm
1/2in.
12.7mm
41-100ft
13-30m
1/2in.
12.7mm
1/2in.
12.7mm
3/4in.
19mm
1/2in.
12.7mm
101-150ft
31-46m
3/4in.
19mm
1/2in.
12.7mm
7/8in.
22.2mm
3/4in.
1.9mm
Note:Neveruseplasticpipe.Checktoconrmwhetheryourlocal
codesallowcoppertubingorgalvanized.
Note:Sincesomemunicipalitieshaveadditionallocalcodes,itis
alwaysbesttoconsultyourlocalauthorityandinstallationcode.
Theuseofthefollowinggasconnectorsisrecommended:
— ANSZ21.24ApplianceConnectorsofCorrugatedMetalTubing
andFittings.
— ANSZ21.45AssembledFlexibleApplianceConnectorsofOther
ThanAll-MetalConstruction
Theaboveconnectorsmaybeusedifacceptablebytheauthority
having jurisdiction. The state of Massachusetts requires that a
exibleapplianceconnectorcannotexceedthreefeetinlength.
▲
►
▼
◄
◄
FLEXIBLE GAS LINE CONNECTION
GAS SUPPLY
TEE HANDLE
FLEX TUBING
FLARE SHUT OFF VALVE
FLARE
FITTING
Figure 7
GasSupplyPressure(inchesw.c.)
Minimum Normal Maximum
NaturalGas 5.0 7.0 14.0
LP(Propane) 10.8 11.0 14.0
ManifoldPressure(inchesw.c.)
Normal(HI)
NaturalGas 3.5
LP(Propane) 10.0
Installing a New Main Gas Cock
Eachapplianceshouldhaveitsownmanualgascock.
Amanualmaingascockshouldbelocatedinthevicinityoftheunit.
Wherenoneexists,orwhereitssizeorlocationisnotadequate,
contactyourlocalauthorizedinstallerforinstallationorrelocation.
Compoundsusedonthreadedjointsofgaspipingshallberesistant
totheactionofliqueedpetroleumgases.Thegaslinesmustbe
checkedforleaksbytheinstaller.Thisshouldbedonewithasoap
solutionwatchingforbubblesonallexposedconnections,andif
unexposed,apressuretestshouldbemade.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE:Thegascontrolsareequippedwithacapturedscrewtype
pressuretestpoint,thereforeitisnotnecessarytoprovidea1/8in.
testpointupstreamofthecontrol.
Whenusingcopperorexconnectoruseonlyapprovedttings.
Theapplianceanditsindividualshutoffvalvemustbedisconnected
fromsupplypipingsystemduringanypressuretestingofthatsystem
attestpressuresinexcessof1/2psig(3.5kPa).
Theappliancemustbeisolatedfromthegassupplypipingsystem
byclosingitsindividualmanualshutoffvalveduringanypressure
testingofthegassupplypipingsystemattestpressuresequalto
orlessthan1/2psig(3.5kPa).
Attention!Ifoneoftheproceduresresultsinpressuresinexcess
of1/2psig(14in.w.c.)(3.5kPa)onthereplacegasvalve,itwill
resultinahazardouscondition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulatorinthegasvalve.Naturalgasmodelswillhaveamanifold
pressureofapproximately3.5in.w.c.(.871kPa)atthevalveoutlet
withtheinletpressuretothevalvefromaminimumof5.0in.w.c.
(1.245kPa)forthepurposeofinputadjustmenttoamaximumof
14.0in.w.c.(3.484kPa).Propanegasmodelswillhaveamanifold
pressure approximately 10.0 in. (2.49kPa) at the valve outlet
withtheinletpressuretothevalvefromaminimumof10.8in.w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0in.w.c.(3.484kPa).