GAS SUPPLY
The gas pipeline can be brought in through the left side of the
appliance.ConsultthecurrentNationalFuelGasCode,ANSIZ223.1
CAN/CGA-B149(.1or.2)installationcode.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat. L.P. Nat. L.P.
0-10ft
0-3m
1/2in.
12.7mm
3/8in.
9.5mm
1/2in.
12.7mm
3/8in.
9.5mm
11-40ft
4-12m
1/2in.
12.7mm
1/2in.
12.7mm
5/8in.
15.9mm
1/2in.
12.7mm
41-100ft
13-30m
1/2in.
12.7mm
1/2in.
12.7mm
3/4in.
19mm
1/2in.
12.7mm
101-150ft
31-46m
3/4in.
19mm
1/2in.
12.7mm
7/8in.
22.2mm
3/4in.
1.9mm
Note:Neveruseplasticpipe.Checktoconrmwhetheryourlocal
codesallowcoppertubingorgalvanized.
Note:Sincesomemunicipalitieshaveadditionallocalcodes,itis
alwaysbesttoconsultyourlocalauthorityandinstallationcode.
Theuseofthefollowinggasconnectorsisrecommended:
— ANSZ21.24ApplianceConnectorsofCorrugatedMetalTubing
andFittings.
— ANSZ21.45AssembledFlexibleApplianceConnectorsofOther
ThanAll-MetalConstruction
Theaboveconnectorsmaybeusedifacceptablebytheauthority
having jurisdiction. The state of Massachusetts requires that a
exibleapplianceconnectorcannotexceedthreefeetinlength.
FLEXIBLE GAS LINE CONNECTION
GAS SUPPLY
TEE HANDLE
FLEX TUBING
FLARE SHUT OFF VALVE
FLARE
FITTING
Figure 7
GasSupplyPressure(inchesw.c.)
Minimum Normal Maximum
NaturalGas 5.0 7.0 14.0
LP(Propane) 10.8 11.0 14.0
ManifoldPressure(inchesw.c.)
Normal(HI)
NaturalGas 3.5
LP(Propane) 10.0
Installing a New Main Gas Cock
Eachapplianceshouldhaveitsownmanualgascock.
Amanualmaingascockshouldbelocatedinthevicinityoftheunit.
Wherenoneexists,orwhereitssizeorlocationisnotadequate,
contactyourlocalauthorizedinstallerforinstallationorrelocation.
Compoundsusedonthreadedjointsofgaspipingshallberesistant
totheactionofliqueedpetroleumgases.Thegaslinesmustbe
checkedforleaksbytheinstaller.Thisshouldbedonewithasoap
solutionwatchingforbubblesonallexposedconnections,andif
unexposed,apressuretestshouldbemade.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
NOTE:Thegascontrolsareequippedwithacapturedscrewtype
pressuretestpoint,thereforeitisnotnecessarytoprovidea1/8in.
testpointupstreamofthecontrol.
Whenusingcopperorexconnectoruseonlyapprovedttings.
Theapplianceanditsindividualshutoffvalvemustbedisconnected
fromsupplypipingsystemduringanypressuretestingofthatsystem
attestpressuresinexcessof1/2psig(3.5kPa).
Theappliancemustbeisolatedfromthegassupplypipingsystem
byclosingitsindividualmanualshutoffvalveduringanypressure
testingofthegassupplypipingsystemattestpressuresequalto
orlessthan1/2psig(3.5kPa).
Attention!Ifoneoftheproceduresresultsinpressuresinexcess
of1/2psig(14in.w.c.)(3.5kPa)onthereplacegasvalve,itwill
resultinahazardouscondition.
Checking Manifold Pressures
Both Propane and Natural gas valves have a built-in pressure
regulatorinthegasvalve.Naturalgasmodelswillhaveamanifold
pressureofapproximately3.5in.w.c.(.871kPa)atthevalveoutlet
withtheinletpressuretothevalvefromaminimumof5.0in.w.c.
(1.245kPa)forthepurposeofinputadjustmenttoamaximumof
14.0in.w.c.(3.484kPa).Propanegasmodelswillhaveamanifold
pressure approximately 10.0 in. (2.49kPa) at the valve outlet
withtheinletpressuretothevalvefromaminimumof10.8in.w.c.
(2.68kPa) for the purpose of input adjustment to a maximum of
14.0in.w.c.(3.484kPa).
2-7/16”
(61mm)
Figure 8