Installation manual

28 SAVIO PLUS COMBI MANUAL
12. Electrical Connections/Wiring Cont.
Room Thermostat Connection:12.3
The room thermostat must be connected
to the terminal block situated next to the
control panel.
Figure 12.6
Any external controls and connection lines
must be rated at 120 VAC but under no
circumstances should external live volt-
age be connected to the room thermostat
link on the boiler.
12
LN
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
120 VAC Control
Terminal Block
Relay Panel Connection:12.4
When connecting any type of external
control, the jumper J in Fig. 12.6 must be
removed.
The room thermostat must be connected
to the “Control Terminal Block” (Fig 12.7).
Figure 12.7
Connect the room thermostat between
terminals 1 and 3 as shown in Fig. 12.7.
Power supply
terminal block
External controls
terminal block
T
Room thermostat
12
LN
3
(120V rating)
The relay control must be connected to
the terminal block situated next to the
control panel.
Figure 12.8
When connecting any type of relay con-
trol, the jumper J in Fig. 12.8 must be re-
moved.
12
LN
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
Connect the dry contact switch of the re-
lay panel to the 120 VAC control terminal
block (Fig 12.9).
Figure 12.9
Connect the dry contact switch to termi-
nals 1 and 3 shown in Fig. 12.9.
Power supply
terminal block
External controls
terminal block
Generic Relay Control
12
LN
3
(120V rating)
T