Installation manual

SAVIO PLUS COMBI MANUAL 31
Piping14.
All external piping components are to be supplied by the installer. It is very important to use a
Primary Secondary piping scheme when an external circulator will be used. Also, when the boiler
is piped in a primary secondary manner, it is necessary to us the central heating ow restrictor
supplied with the boiler. The ow restrictor ensures that there will be enough back pressure to
make the central heating ow switch in a low head loss piping system like primary secondary.
Installation of ow restrictor: The ow restrictor is installed inside the pipe tail that
attaches to the boiler. Place the ow restrictor into the
gasket for the central heating supply pipe tail. Place
the gasket on the pipe tail so the ow restrictor seats
into the pipe tail. Then install the pipe tail onto the
boiler.
There are two methods for accomplishing a Primary Secondary piping system. The rst is to
use two closely spaced tees for the boiler supply and return. An example is shown below in
Figure 14.1. The run legs should be sized so that there is no excessive head loss on the exter-
nal circulator that is installed. In most circumstances 1 ¼” piping will be the best choice. When
the boiler is piped in this way, the external circulator will not have any hydraulic effect on the
SAVIO Plus Combi. This is essential to ensure that the ow switch will operate properly.
Figure 14.1
The second method is a hydraulic separator. Hydraulic separators are available commercially;
however you can also construct your own. An example of a hydraulic separator is given in Figure
14.2. It is important that the separator be at least 2” in size to ensure proper performance.
Figure 14.2
Must be less than 8"
Boiler
Return
Boiler
Supply
System
Return
System
Supply
1 ¼”
¾”
2"
No more than 8"
At least 16"
1 ¼”
¾”
System supply
System return
Boiler supply Boiler Return