Service Manual

SERVICE PROCEDURE ACE-I
Heating Element Testing
1. STOP, DANGER! Turn power “OFF” to water heater.
2. Open control panel access door.
3. Disconnect wires from heating element.
4. Set multi-meter to “ohms” setting.
5. Touch probes of multi-meter to screw
terminals of heating element
(see illustration 1).
6. Reading should be 12.8 ohms (±6%) for a 240
volt, 4500 watt element, see table below for other elements.
A reading outside the range using the formula
above (±6%), indicates a bad element and the
element must be replaced.
Test for Open or Burned Out Element.
DANGER
High voltage exposure. To avoid hazard to
Life or property, be sure power is turned
OFF to water heater while performing this
procedure.
Test For Grounded Heating Element
(damaged heating element with short circuit to ground).
1. STOP, DANGER! Turn power “OFF to water heater.
2. Open control panel access door.
3. Disconnect wires from heating element.
4. Set multi-meter to “ohms” setting.
5. Touch one probe of multi-meter to either screw
terminal of heating element and the other on
the element flange (see illustration 2). There
should be no reading on the ohm meter. Any
reading indicates a grounded element and the
element must be replaced. Repeat this step for
the other screw terminal.
Ohms = Volts
2
Watts
Element Screw Terminals
Element
Screw Terminal
Element Flange
Illustration 1
Illustration 2
Page 15
NOTE
Disconnect
element
Wires
NOTE
Disconnect
element
Wires
Ohms of electrical Resistance
For commonly Used Elements
Voltage Rating of Element
Element
Wattage 208 240 480 600
2000 21.6 28.8 115.2 180
3000 14.4 19.2 76.8 120
4000 10.8 14.4 57.6 90
4500 9.6 12.8 51.2 80
5000 8.7 11.5 46.1 72
6000 7.2 9.6 38.4 60
9000 4.8 6.4 25.6 40
15
15