Spec Sheet

719-B-1112-A Printed in U.S.A.
Thermal efficiency up to 85%
ASME 160 psi working pressure heat
exchanger
ASME "H" stamp, designed and certified
for potable water use
Flanged bronze water connections
Glass-lined headers
External header gaskets
125 psi (861 kPa) ASME rated pressure
relief valve
Flow switch, mounted and wired
Temperature/pressure gauge
Pump, mounted and wired
Multiple operating gas valve/pressure
regulators
Manual “A” gas valve
Washable intake air filter
Multiple, removable burner trays
Stainless steel burners
Built-in draft fan for Category I or III vent
systems
Air pressure switch
Burner site glass
24V control system
115/24VAC transformer
Ignitor access panels
Energy Management Monitor (EM
2
)
pump time delay
Manual reset high limit
Automatic reset high limit (500-2000 only)
Electronic PID staging control with LCD
and touchpad
PC board for electrical connections
External controller connections with
selector switch
Hot surface ignition
On/Off toggle switch
Pump time delay
Diagnostic lights
Less than 10 ppm NOx (500-2000 only)
Less than 30 ppm NOx (200-400 only)
All models can be converted to either
indoor use or outdoor use. For outdoor
use, you must order exhaust vent and air
intake vent (consult factory for part
numbers)
Standard Features
Optional Equipment
Copper-nickel heat exchanger
Normally open vent valve (500-2000 only,
see IRI Package)
Low water cutoff
Motorized gas safety valve
(500-2000, see LDS Package)
Double stack stand (500-2000 only)
Reverse Heat Exchanger - switches the
inlet and outlet to left side and pump to the
right side
Indoor Venting Accessories (required for
sidewall venting)
CSD-1 Package includes:
Size 500-2000:
Single Try Ignition, High and Low Gas
Pressure Switches, and Gas Regulator.
Excludes Low Water Cutoff.
IRI Package, added to the CSD-1 package
includes:
Size 500-2000:
Single Try Ignition, High and Low Gas
Pressure Switches with Manual reset,
Normally Open Vent Valve, Safety Valve
with Gas Regulator and Leak Test Valve.
Excludes Low Water Cutoff
LDS Package includes:
Size 500-1000:
Safety Valve with Gas Regulator, High Gas
Pressure Switch and Leak Test Valve.
Size 1250-2000:
Solenoid Safety Valve, Motorized Valve
with Proof of Closure, Leak Test Valve,
High and Low Gas Pressure Switches.
Clearances
*When vent and/or air is connected to the back, 36" (91cm) is suggested.
inch cm inch cm
Left Side 1 2.5 24 61
Right Side 1 2.5 24 61
Top 1 2.5 12 30
Back* 1 2.5 12 30
Front 1 2.5 36 91
Vent
APPLIANCE
SURFACE
REQUIRED CLEARANCE FROM
COMBUSTIBLE MATERIAL
SUGGESTED SERVICE
ACCESS CLEARANCES
Per venting supplier’s instructions
Power (HP) Current (Amps)
Model Numbers Soft Normal
Hard Soft Normal Hard
BWCV0200
1
3
1
3
3
4 2.8 2.8 7.2
BWCV0300
1
3
1
3
3
4 2.8 2.8 7.2
BWCV0400
1
3
1
3
3
4 2.8 2.8 7.2
BWCV0500
1
3
1
3
3
4 2.8 2.8 7.2
BWCV0750
1
3
1
3
3
4 2.8 2.8 7.2
BWCV1000
1
3
1
2
3
4 2.8 5.2 7.2
BWCV1250
1
3
1
2
3
4 2.8 5.2 7.2
BWCV1500
1
3
3
4
3
4 2.8 7.2 7.2
BWCV1750
3
4
3
4
3
4 7.2 7.2 7.2
BWCV2000 1 1 1 9.8 9.8 9.8
Motor Electrical Data
WATER CATEGORY
©2012, Bradford White Corporation. All rights reserved.
Ambler, PA
For U.S. and Canada field service, contact your professional installer or local Bradford White sales representative.
Sales 800-523-2931
Fax 215-641-1670 / Technical Support 800-334-3393
Fax 269-795-1089
Warranty 800-531-2111
Fax 269-795-1089
International: Telephone 215-641-9400
Telefax 215-641-9750 / www.bradfordwhite.com
Sales / Technical Support 866-690-0961 / 905-238-0100