Model BEB
Specication
Contractor shall supply and install Qty.: _____ Bradford White Model No. _______ boiler(s).
The boiler shall be a Bradford White Electric Boiler Model ______, rated at the output shown on the schedule. The vessel shall
be ASME "H" stamped and National Board registered with a maximum working pressure of 30 psi (optionally 125 psi). The unit(s)
shall be fully tested using standard UL834, shall bear the CSA mark, and shall meet the requirements of ASME CSD-1.
The vessel shall have a capacity of 40 gallons. It shall have 3" NPT threaded inlet and outlet nozzles. The outlet nozzle shall be
located on the top of the vessel. The inlet nozzle shall be located on the left side of the vessel. A ½" air vent shall be included.
The immersion heating elements shall be installed in the top of the vessel and threaded into vessel for easy servicing (water draw-
down not required.)
The boiler shall be available in 208V, 240V, 480V and 600V three phase voltages, and shall include a dedicated 15A 120V single
phase control circuit (general service) that includes a primary pump relay. Terminals shall be provided on the boiler for connection
to an emergency stop switch. Wiring within the main cabinet shall be rated at 75°C or higher.
The boiler shall have a built-in digital temperature control with display. The control shall include supply and return water
temperature sensing. The control shall have multiple boiler, lead-lag capabilities, including provisions for stage rotation. Automatic
turn-down as the load decreases, and outdoor reset with auto-detect feature shall be included. 0-10VDC connections shall be
standard, to allow for external boiler control. Gateways for Modbus, BACnet and LonWorks protocols shall be available from the
boiler manufacturer. The control assembly shall include a six-function alarm LED.
The boiler shall include a mounted low water cuto󰀨 with manual reset, a manual reset temperature high limit set at 220°F, an
automatic reset high temperature limit set at 210°F, and a temperature and pressure gauge.
The heating elements shall be constructed using incoloy sheathing for long service life. The low-watt density heating elements
shall be 30" long. Contactors used to operate the heating elements shall be rated for 500,000 cycles, and each contactor shall
have a staging light. The boiler shall have a circuit breaker for each element, providing convenient and safe disconnection of
individual elements.
The boiler shall be no more than 30" wide, to t through a typical service door. The cabinet shall include a full-length hinged door
with an included lockable T-handle. The inside dead front panel shall include an integral door safety interlock switch. The cabinet
shall have a split cover top for easy access to the heating elements.
The vessel shall be wrapped with 3" insulation and be fully enclosed in a 14-gauge cabinet. The cabinet and vessel shall be
attached to a 10-gauge structural steel base. The base shall include integral fork pockets for easy maneuvering during installation.
Both base and cabinet shall be painted with powder coat enamel.
A mounted control enclosure shall be included. The control enclosure shall contain all boiler controls and adjustments. The boiler
operator shall not be required to enter main cabinet for resets or other functions. A window shall be included on the door of the
control enclosure to permit viewing of monitor and alarm LED's.
The boiler shall include a 5-year limited warranty on the vessel and a 1-year limited warranty on the parts.
Standard features shall include:
ASME pressure vessel
National Board & CRN registration
Meets ASME CSD-1 requirements
ASME 30 psi pressure rating and PRV
(125 psi optional)
SCCR rated at 5 kW
Temp. & pressure gauge
3" inspection opening
3" NPT water connections
Integrated ½" air vent
Supply & return water temp sensing
Digital temp control with display
Multiple boiler lead/lag control
0-10VDC external boiler control
Adjustable outdoor reset
Manual reset high limit, 220°F
Auto reset high limit, 210°F
Low water cuto󰀨 with manual reset
Stage active indicator lights
Circuit breakers or fuse protection on
each stage
Emergency shut-down connection point
Safety door interlock
Lockable door latch