Installation / Operation Instruction Manual

Page 1
Brute LX
Figure 1. Opening the 100, 125, 150, 175, and 220
Figure 2. Model Nomenclature
1.1 Introduction
This manual provides information necessary for the
installation, operation, and maintenance of Bradford
White Corp Brute LX appliances. Read it carefully
before installation. All application and installation
procedures should be reviewed completely before
proceeding with the installation. Consult the Bradford
White Corp factory, or local factory representative, with
any problems or questions regarding this equipment.
Experience has shown that most operating problems are
caused by improper installation.
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest
1.3 Rating Plate
The Rating Plate is located on the metal pan behind
the lower plastic panel. Figure 1. It contains Model
Nomenclature, Manufacture Date, Model Number,
Serial Number, Output Rating, and all other information
pertaining to your Brute LX. .
1.2 To Open the Brute LX
To open the Brute LX for maintenance and servicing,
the upper and lower plastic panels are designed to 'pop'
o when they are pulled forward. See Figure 1 and
Figure 3. This will expose the top metal panel which
covers the heat exchanger, and the lower panel which
holds the low voltage connections and covers the pump
and other lower components.
To remove these panels for further access into the
Brute LX, there are two screws that hold each panel in
place. Remove the 2 screws on the upper panel and slide
the upper metal panel up and out. For the lower panel,
remove the 2 screws and hinge the lower metal panel
downward.
The center panel containing the On/O Switch, Gauges,
and User Interface is not removable.
Edition “National Fuel Gas Code” or
2) CSA B149.1 “Natural Gas and Propane Installation
Code” and with the requirement of the local utility or
other authorities having jurisdiction. Such applicable
requirements take precedence over the general
instructions contained herein.
All electrical wiring is to be done in accordance with
the local codes, or in the absence of local codes, with: 1)
The National Electrical Code ANSI/NFPA No. 70-latest
Edition, or 2) CSA STD. C22.1 “Canadian Electrical
Code - Part 1”. This appliance must be electrically
grounded in accordance with these codes.
Nomenclature
(1) Label
B = Brute
(2-3) Series Designation
LX = LX Series Heat Exchanger
(4) Usage
H = Modulating Boiler
C = Combination Boiler and Water Heater
(5) Conguration
W = Wall Hung
(6-8) Size
50 = 50,000 BTU/hr input
75 = 75,000 BTU/hr input
100 = 100,000 BTU/hr input
125 = 125,000 BTU/hr input
150 = 150,000 BTU/hr input
175 = 175,000 BTU/hr input
220 = 220,000 BTU/hr input
(9) Fuel
N = Natural Gas
P = LP Gas (propane)
(10) Altitude
A = Up to10,000 Feet: de-rate applies
*
(11) Revision
1 = First version
(12) Options Code
X = Standard
L=Lowwatercuto󰀨
(13) Pump Options
N = With Pump
1.4 Model Nomenclature
The Model Nomenclature is shown on your Rating Plate
and consists of a series of letters and numbers
( Nomenclature ) that further identies the
characteristics of your Brute LX. See Figure 2.
2 3 4 5 6 7 8 9 10 11 12 13
L X A X N
SERIES
LX - SERIES
HEAT
EXCHANGER
LABEL
BRUTE
USAGE
H - HYDRONIC
C - COMBI
UNIT
SIZES
MBTU/h
50
75
100
125
150
175
220
FUEL
N - NATURAL
P - PROPANE
CONFIG
W - WALL
ALTITUDE
A - 0-10,000 FEET
REVISION
1 - FIRST
OPTIONS
X -
STANDARD
L - LWCO
PUMP OPTIONS
N - WITH PUMP
1
B
*
For high altitude applications, boiler must be
de-rated 4% per 1000 feet above 2000 feet.
*