6.7 Condensate Trap Installation
The condensate kit for your unit is part of the
installation kit. See Section 1.11.
For wall mounted models sized 50 and 75 MBH,
fasten the condensate trap to the condensate tray using
the two hose clamps and the hose. See Figure 12. Then
secure the condensate trap to the unit using the wire-tie.
A condensate drain must be installed to prevent
accumulation of condensate. When a condensate pump is
not used, the tubing must continuously slope downward
toward the drain with no spiraling.
Consult local codes for the proper disposal method for
the condensate.
For Condensate Trap Installation Instructions for
larger models, please see the next page.
CAUTION
Condensate is mildly acidic (pH=5), and may harm
someoordrainsand/orpipes,particularlythose
that are metal. Ensure that the drain, drainpipe, and
anything that will come in contact with the condensate
can withstand the acidity, or neutralize the condensate
before disposal. Damage caused by failure to install
a neutralizer kit or to adequately treat condensate
will not be the manufacturers responsibility.
Contact Bradford White to order Kit# A2123601
___________________________________________
Figure 12. Condensate Trap for
50 - 75 MBH Brute LX
Wire-tie
Two hose
clamps and
the hose
Wire-tie into
the bent down
tab to hold
condensate
trap in place
View when assembled