The FT Series Wall Mounted, Combination Boiler
Page 19
The FT is standard as a Natural Gas Boiler and
must be converted if propane is the desired gas, unless
specically manufactured for propane.
Adequate drainage
The appliance should be installed not to damage
the adjacent area. If such locations cannot be
avoided, it is recommended that a suitable drain
pan, adequately drained, be installed under the
appliance. The pan must not block combustion air
ow.
Connecting the Water Supply
To conserve water and energy, insulate all water
piping—especially the hot and recirculation water
lines. Never cover the drain or pressure relief valve.
Having a backow preventer in the cold water
supply line will prevent thermal expansion
backow. Contact the water supplier or local
plumbing inspector for information about how to
control this situation.
If overheating occurs or the gas supply fails to shut
o󰀨, turn o󰀨 the manual gas valve.
This installation must conform with below section
“Air for Combustion and Ventilation” of the
National Fuel Gas Code, ANSI Z224.1/NFPA 54,
or Sections 8.2, 8.3 or 8.4 of Natural Gas and
Propane Installation Code, CAN/CSA B149.1, or
applicable provisions of the local building codes.
When an existing Cat I appliance is removed or
replaced, the original venting system may no longer
be sized to properly vent the attached appliances.
Under no circumstances should an improperly sized
vent be used. An improperly sized vent may cause
operational and safety problems, and could result in
serious injury, death, or property damage.
CAUTION
CAUTION
NOTICE
The instructions for the installation of the venting
system shall specify that the horizontal portions of
the venting system shall be supported to prevent
sagging; the methods of and intervals for support
shall be specied. These instructions shall also
specify that the venting system:
Category I, II and IV boilers must be installed so that
horizontal sections have an upward slope away from
the boiler of at least ¼ inch per foot (21 mm/m) to
prevent accumulation of condensate; and
For Category II and IV boilers, where necessary,
have means provided for drainage of condensate.
NOTICE
For long, trouble free operation, it is critical that the
FT unit has always access to clean combustion air,
either drawn from an inside space (per section 4.3.1)
or external (per section 4.3.2).
Do NOT allow contaminated indoor air (either by
internal dust, sheet rock, PVC or CPVC pipe debris
dust or similar contamination) to be drawn in through
the air intake connection. If the unit must operate
under job site conditions, always ensure availability
of fresh air and protect the unit accordingly.
For ducted combustion air from the outdoors,
follow the guidelines provided in Sections 4.6
through 4.8 and make sure that clean air is always
available for combustion.
During assembly of the air intake system,
make sure that any PVC or CPVC pipe debris due
to cutting pipe is fully removed and all connecting
surfaces are smooth and free of contamination.
AVIS
Les instructions d'installation du système
d'évacuation doivent préciser que les sections
horizontales doivent être supportées pour prévenir
le échissement. Les méthodes et les intervalles
de support doivent être spéciés. Les instructions
doivent aussi indiquer les renseignements suivants:
les chaudières de catégories I, II et IV doivent
présenter des tronçons horizontaux dont la pente
montante est d'au moins ¼ po par pied (21 mm/m)
entre la chaudière et l'évent; les chaudières de
catégories II et IV doivent être installées de façon à
empêcher l'accumulation de condensat;
et si nécessaire, les chaudières de catégories II et IV
doivent être pourvues de dispositifs d'évacuation du
condensat.