Installation / Operation Instruction Manual

The FT Series Heating Only, Boiler
Page 75
8.1 Annual Startup & General Maintenance
Regular Maintenance
- This Manual should be placed in a safe and dry
location near the Boiler. Maintenance instructions
should be carried out by the following guidelines.
Maintenance procedures [ Daily ]
- Check that the boiler casing is closed.
Check if there is any problem with the Boiler casing
and the two upper and lower screws are tightened
well. Boiler casing must be closed while it is
running.
- Check the power source.
Make sure that the power cord is correctly
connected. The main power line is connected to
the manual switch box inside a Boiler. (Power line
through the strain relief in the bottom of the boiler
casing and x it.)
- Check the status of the Control Display
Check status of the power supply. Please check for
any debris on the button.
Maintenance procedures [ Monthly ]
- Check the vent pipe.
Visually inspect the ue gas vent piping for detecting
any signs of blockage, leakage or deterioration
of the piping. Please contact a qualied service
technician immediately if you nd any problem.
- Check the air inlet pipe.
Visually inspect the air inlet to be sure it is
unobstructed. Inspect entire length of air piping
for ensuring that piping is intact and all joints
are properly sealed. Call your qualied service
technician if you notice any problems.
- Check the relief valve.
Inspect the Boiler relief valve and the relief valve
discharge pipe for any signs of weeping or leakage.
If the relief valve often weeps, immediately contact
your qualied service technician for inspecting the
Boiler and system.
- Check the condensate outlet.
While the Boiler is running, check the discharge end
of the condensate drain tubing.
Make sure that no ue gas is escaping from the
condensate drain tubing.
If ue gas is continuously escaping, it is a serious
problem. Call your qualied service technician for
inspecting the Boiler and condensate line. Also, rell
the condensate trap if problem persists regularly.
- Check the vent terminal screen vent (rodent
screen).
If you encounter a problem of combustion
specications, visually inspect the terminal screen.
And then replace it with spare parts or clean the
screens.
SECTION 8 Maintenance
WARNING
WARNING
To prevent potential severe personal
injury, death or substantial property
damage, remove all contaminates or
contaminated materials immediately
from the area around the boiler.
If exposed to contaminated materials,
call a qualied service technician to
inspect the boiler for possible damage
from acid corrosion.
DO NOT store combustible materials,
gasoline or any other ammable vapors
or liquids near the Boiler. Remove them
immediately or store them other places.