SECTION 9 Parameter Tables (MGH and MGV)
Table 23. MGH (Boiler) Parameter and Range Table (next 3 pages)
Hour
x x
Hour
Minute
x x
Minute
Month
x x
Month
Day
x x
Day
Year
x x
Year
CH1 Enable/Disable x N/A
CH1 Setpoint x x °F/C
CH1 Priority x N/A
CH1 On Hysteresis x °F/C
CH1 Off Hysteresis x °F/C
CH1 Proportional Gain x N/A
CH1 Integral Time x Seconds
CH1 Derivative Time x Seconds
Max Power x %
CH2 Enable/Disable x N/A
CH2 Setpoint x x °F/C
CH2 Priority x N/A
CH2 On Hysteresis x °F/C
CH2 Off Hysteresis x °F/C
CH2 Proportional Gain x N/A
CH2 Integral Time x Seconds
CH2 Derivative Time x Seconds
Max Power x %
DHW Enable/Disable x N/A
DHW Setpoint x x °F/C
DHW Priority x N/A
DHW On Hysteresis x °F/C
DHW Off Hysteresis x °F/C
DHW Proportional Gain x N/A
DHW Integral Time x Seconds
DHW Derivative Time x Seconds
DHW Offset x x °F/C
Max Power x %
Outdoor Reset Enable/Disable
x
N/A
Maximum Outdoor Temperature
x
°F/C
Minimum Outdoor Temperature
x
°F/C
Maximum Water Temperature
x
°F/C
Minimum Water Temperature
x
°F/C
Address
x
N/A
Dynamic Address
x
N/A
Lost Lead Backup Setpoint
x
°F/C
Lag On Hysteresis
x
°F/C
Lag Off Hysteresis
x
°F/C
Cascade CH Setpoint
x x
°F/C
Cascade CH Proportional Gain
x
N/A
Cascade CH Integral Time
x
Seconds
Cascade CH Derivative Time
x
Seconds
Cascade CH Priority
x
N/A
0
10
0
0
10
0
0 F
40 F
20 F
0
10
5
1
5
3
0 F
20 F
10 F
DHW
Disable
Enable
Enable
40 F
200 F
2
0 F
20 F
10 F
40 F
210 F
180 F
Maximum Default
Time & Date
NA
NA
NA
Boilers
User
Installer
Minimum
NA
NA
NA
NA
NA
NA
CH1
Disable
Enable
Enable
NA
NA
NA
NA
NA
NA
0 F
20 F
10 F
0
10
5
1
5
0 F
20 F
10 F
CH2
Disable
Enable
Enable
40 F
210 F
170 F
0
10
2
50%
100%
100%
180 F
0
10
2
50%
100%
100%
0 F
20 F
10 F
0
10
5
1
5
1
0 F
20 F
10 F
50%
100%
100%
Outdoor Reset
Disable
Enable
Disable
0
10
2
0
10
0
40 F
210 F
180 F
40 F
210 F
120 F
0 F
140 F
65 F
-40 F
100 F
0 F
40 F
210 F
180 F
0 F
20 F
10 F
Cascade CH
0
8
0
0
8
0
0
10
5
0
10
2
0 F
20 F
10 F
40 F
210 F
180 F
0
10
0
1
5
4
Unit