Installation / Operation Instruction Manual

Table Of Contents
Page 117
Outlet
Sensor Drift
Dual element sensor readings do not
agree.
Manual-reset Condition
Annunciation on Navigation Bar
Check the sensor and wiring. Repair or replace as needed.
The outlet probe is a dual element probe with 10K and 20K
thermistors. A quick test is to measure resistance and verify
one resistance is double the other. Replace if necessary.
Measure the resistance of each element of the sensor and
compare to the resistance table below. Replace if necessary.
Temp (°F)
10K
20K
Resistance (Ω)
Resistance (Ω)
68
12555
25099
86
8025
16057
104
5279
10569
122
3563
7139
140
2463
4937
158
1739
3489
176
1253
2514
194
919
1845
212
685
1376
Inlet Sensor
Inlet sensor is damaged or not connected.
Manual-reset condition
Annunciation on Navigation Bar
Check the sensor and wiring. Repair or replace as needed.
Measure the resistance of the sensor and compare to the
resistance table below. Replace if necessary.
Temp (°F)
Temp (°C)
Resistance (Ω)
68
20
12555
86
30
8025
104
40
5279
122
50
3563
140
60
2463
158
70
1739
176
80
1253
194
90
919
212
100
685
Burner
Parasitic
Flame
Sensing flame on burner prior to ignition.
Manual-reset Condition
Annunciation on Navigation Bar
Inspect flame and wiring for damage and continuity. Replace if
necessary.
Burner Max
Trials
The maximum attempts for ignition has
occurred, without sensing flame.
Manual-reset Condition
Annunciation on Navigation Bar
Verify supply and manifold gas pressures satisfy installation
requirements.
Verify the proper intake and venting.
Inspect the burner.
Check pilot and main valve wiring and operation.
Check ignition transformer electrode, flame detector wiring and
position.
Additional
High Limit
Outlet water temperature has exceeded the
additional high limit setting
Auto-reset Condition
Annunciation Warning Additional high
limit” on Message Screen
Verify the system is full of water and all air has been purged
from the system.
Verify the boiler/heater is piped properly into the heating
system.
Check for proper pump operations.
Check the additional high limit set point.
Lockout: Outlet Probe Drift
Lockout: Inlet Probe
Lockout: Burner Parasitic Flame
Lockout: Burner Max Trials
Condition
Information
Corrective Action
Flow Switch
Insufficient flow at the outlet of the
boiler/heater
Auto-reset Condition
Annunciation Warning Flow switch open
on Message Screen
Faulty boiler/heater pump replace pump.
Faulty pump contactor replace contactor.
Blown boiler/heater pump fuse replace fuse F14 on the
control board.
Low Water
Cut Off
Insufficient water level in the boiler/heater
heat exchanger.
Manual-reset Condition
Annunciation on Navigation Bar
Reset the LWCO from the reset button on the LWCO module.
Verify the system is full of water and all air has been purged
from the system.
Check for loose jumpers if the LWCO is not installed.
Manual
Reset High
Limit
Outlet water temperature has exceeded the
manual reset high limit setting
Manual-reset Condition
Annunciation on Navigation Bar
Verify the system is full of water and all air has been purged
from the system.
Verify the boiler/heater is piped properly into the heating
system.
Check for proper pump operations.
Check the manual reset high limit set point.
Auto Reset
High Limit
Outlet water temperature has exceeded the
auto reset high limit setting
Auto-reset Condition
Annunciation Warning High limit auto
error” on Message Screen
Verify the system is full of water and all air has been purged
from the system.
Verify the boiler/heater is piped properly into the heating
system.
Check for proper pump operations.
Check the manual reset high limit set point.
Pressure
Switch
Blocked flue switch contacts are open
Manual-reset Condition
Annunciation on Navigation Bar
Check the wiring connections to the switch. The wires should
be connected to the common and normally open terminals.
Check reference hose and tubing connected to the pressure
switch for blockage/obstruction.
Faulty switch replace switch.
Verify blower is operating replace if necessary.
High Gas
Pressure
The high gas pressure switch has tripped
Manual-reset Condition
Annunciation on Navigation Bar
Refer to Section 3 for Gas Supply and Piping information.
Verify supply and manifold gas pressures satisfy installation
requirements.
Low Gas
Pressure
The low gas pressure switch has tripped
Manual-reset Condition
Annunciation on Navigation Bar
Refer to Section 3 for Gas Supply and Piping information.
Verify supply and manifold gas pressures satisfy installation
requirements.
Condensate
Level
Condensate trap water level is high
Auto-reset Condition
Annunciation Warning Condensate level
on Message screen
Check condensate trap for proper drainage
Check condensate trap for stuck level switch
Outlet
Sensor
Outlet probe is not connected
Manual-reset Condition
Annunciation on Navigation Bar
Check the sensor and wiring. Repair or replace as needed.
The outlet probe is a dual element probe with 10K and 20K
thermistors. A quick test is to measure resistance and verify
one resistance is double the other. Replace if necessary.
Measure the resistance of each element of the sensor and
compare to the resistance table below. Replace if necessary.
Temp (°F)
10K
20K
Resistance ()
Resistance ()
68
12555
25099
86
8025
16057
104
5279
10569
122
3563
7139
140
2463
4937
158
1739
3489
176
1253
2514
194
919
1845
212
685
1376
Lockout: Low Water Cut Off
Lockout: Man Reset High Limit
Lockout: Burner APS Switch
Lockout: High Gas Pressure
Lockout: Low Gas Pressure
Lockout: Outlet Probe
SECTION 12 Troubleshooting (continued)