Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 36
Table 18. Electrical Data
Full Load Amperage
Minimum Circuit Ampacity
Max Over-current Protection
Size
Voltage 120 240/220 208 1Ф 120 240/220 208 1Ф 208 3Ф 480 600
FLA 6.2 3.4 3.6
18.6
10.1
12.5 7.5 3.5 4.4
MCA 7.8 4.2 4.5 23.3 12.7 15.6 9.4 4.4 5.5
MOP
20 15 15 30 25 25 15 15 15
Size
Voltage 208 3Ф 480 3Ф 600 3Ф 208 3Ф 480 600
FLA 9.5 4.4 3 9.9 3.6 4.5
MCA
12 6 4 12 5 6
MOP 20 15 15 20 15 15
1600
2000
2500/3000
3500/4000
Size
Voltage 120 240/220 208 1Ф 120 240/220 208 1Ф 208 3Ф 480 600
FLA 6.2 3.4 3.6
18.6
10.1
12.5 7.5 3.5 4.4
MCA 7.8 4.2 4.5 23.3 12.7 15.6 9.4 4.4 5.5
MOP
20 15 15 30 25 25 15 15 15
Size
Voltage
208 3Ф 480 3Ф 600 3Ф 208 3Ф 480 600
FLA 9.5 4.4 3 9.9 3.6 4.5
MCA
12 6 4 12 5 6
MOP 20 15 15 20 15 15
1600
2000
2500/3000
3500/4000
Three Phase
600 480 208
L1 P BR Blk
L2 V O Red
L3 T Y BL
Single Phase
120 240 208
L1 Blk Blk Blk
L2 Wht Red Red
Table 19. VoltagePhaseColorIdentication
Figure 17. Wiring Access
This unit is provided with an electrical
junction box in the rear panel for main
power connections. See Figure 17.
All power wires are factory installed
between this junction box and the main
high voltage box at the front of the
unit. The unit is available with multiple
voltage packages to adapt to customer
needs ranging from 120-600 volts with
single or 3 phase versions. Refer to the
rating plate and Table 18 for appropriate
voltage and current ratings.
As a common industry practice, the
manufacturer has color coded the single
and three phase wires as shown in
Table 19.
On single phase models, the incoming
voltage will be protected by the
appropriate circuit breaker, sized and
installed by a qualied electrician/
authorized personnel. The 120-volt and 24-volt systems
will be protected with resettable fuses mounted in the
top of the high voltage box. The 24-volt transformer
is also redundantly protected by its integrated 4 amp
resettable fuse.
On three phase models, a step down transformer (which
is protected using an appropriate din rail mounted circuit
breaker) generates 120-volt single phase to power the
7.B Main Power Connections
24-volt transformer. The 120-volt and 24-volt outputs of
either transformer are protected with resettable fuses
mounted in the top of the high voltage box. The 24-
volt transformer is also redundantly protected by its
integrated 4 amp resettable fuse.
All power connections must be run through the
back panel as shown in Figure 17.
Field Electrical
Connections at the Terminal
Block on the Control Panel.
See Figure 18 on page 37
Available Electrical Raceway
Available Knockouts for System
Sensor and/or modbus, etc.
VIEW from
the
BACK
Shown with outside panels
removed for full servicing.
Junction Box for Main Power
Connections