Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 37
Figure 19. Field Connection Terminal Block
7.C Control Panel Layout
Manual Reset
High Limit (optional)
Auto Reset
High Limit (optional)
Boiler Controller
(shown
uncovered)
Terminal
Block
Low Water
Cuto
Figure 18. Control Panel Components
output current of 1.5 amps. Boiler pump functionality is
congured using the touch screen.
Auxiliary – no functionality is available on this unit.
7.D.2 Dry Contacts
DHW Pump - if connecting a domestic hot water (DHW)
pump, use terminals 21 and 22 (See Figure 19) as this
is a dry contact, the DHW pump supply voltage or DHW
7.D Field Connections
Wiring for all Field Connections must be run along the
inside face of the available electrical raceway to the
back of the unit. See Figure 17. and See Figure 19.
7.D.1 Power
Boiler Pump – if connecting a boiler contactor or pump,
use terminals 17 (neutral) and 18 (line voltage). The
output of these terminals is 120VAC with a maximum
Lead
Lag