Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 66
8.D.1 CH (Central Heat)
“CH” stands for “Central Heat.” It is used for
space heating demands.
On the Congure Screen, touch the CH
thermometer icon to navigate to the CH
Selection Screen
There are two identical heat demands, CH1
and CH2, each with independent control
algorithms and independent inputs on the input
terminal strip, see 7.D on page 37
From the CH Selection Screen, touching CH1
navigates to the CH1
CONFIGURATION
8.D.1.a CH1 (Central Heat, One)
CH1 is one of the heat demands available. The CH1 Conguration Screen allows adjustment of the
following parameters:
•
Ena ble/Disable - This allows CH1 to be enabled or disabled. The default setting is Enabled.
•
Set Point - This is the temperature set point for CH1.
•
PID - This allows adjustment to PID algorithms.
•
Max Power - Allows the unit to be de-rated to a percentage that will reduce short cycling.