Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 69
8.D.4 Cascade (Lead / Lag)
An installation with two or more units may be congured for cascade operation (Lead / Lag). Up to eight units can be
cascaded and controlled together.
To navigate to the Cascade Screen, touch the Cascade Icon on the Conguration Screen.
The Cascade Screen provides four navigation icons to congure the system for cascade operations. These navigation icons are:
•
Cascade CH – This icon navigates to the setup screen for hydronic boiler cascade operations. This icon is available on hydronic
boilers (MGH) only.
•
Cascade DHW – This icon navigates to the setup screen for water heater cascade operations. This icon is available on water
heaters (MGV) only.
•
Rotation – This icon navigates to the cascade rotation screen.
•
Redundancy – This icon navigates to the setup screen for cascade Leader redundancy options.
About Cascading (Lead / Lag)
The Lead boiler/heater uses the Base Load Value to determine when to re the
Lag units and at what ring rate. The Base Load Value should be adjusted based
on the number of units installed, with a default value of 65%. Recommended base
load values based on the number of units installed is shown in the table below.
The Base Load Value is adjustable via the DU with installer login credentials.
Upon an active cascade heat demand, the Lead boiler/heater will dictate which
unit will re rst based on the cascade rotation logic. As the ring rate of this unit
reaches the Base Load Value, once the Min On Time timer expires, the next unit in
the sequence will re and both units will modulate up or down together at the same
ring rate in reaction to changes in heat demand. This pattern will continue until
the ring rates of all cascaded units reach the base load value. Once all units are
ring at the base load value, the ring rate can exceed the base load value, with
all units maintaining the same ring rate. Refer to the Lead / Lag gures below for
additional clarication.
With boilers/heaters ring at the same ring rate, minimum ring rates need to be
taken into consideration. Units with varying turndown ratios can be cascaded
together, therefore, the unit with the highest minimum ring rate dictates the
minimum ring rate of the total cascaded system. For example, if a 5:1 unit is
cascaded with a 20:1 unit, and the 5:1 unit has reached the base load value, the
20:1 will be called to run. The 20:1 will re at the same ring rate as the 5:1, which
CONFIGURATION
Table 20. Recommended
Base Load Values
Boiler Qty Recommended
Base Load
1 N/A
2 65%
3 50%
4 40%
5 40%
6 40%
7 40%
8 40%
NOTE: A system supply sensor
(supplied with each unit) must be
installed and connected to the
Lead boiler/heater. The Lead
boiler/heater will use this system
supply sensor as the temperature
control sensor for cascade
operations.