Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 79
8.D.6 Pumps
The Pump Conguration Screen allows adjustment of the following 7 parameters:
• Boiler Pump Control
– This parameter provides the ability to set the boiler pump functionality to be:
Auto – the pump will turn on automatically upon a call for heat.
Always On – the pump will run continuously.
O Dur ing DHW – the pump will not turn on during a DHW heat demand.
• Boiler Pump Post Circulation
– This parameter is the amount of time the boiler/heater pump will continue to run after a
heat demand has been satised or after a lock-out condition has occurred.
• DHW Pump Control
– This parameter provides the ability to set the DHW pump functionality to be:
Auto – the pump will turn on automatically upon a call for heat.
Always On – the pump will run continuously.
Disable – the pump will not turn on upon a DHW heat demand.
• DHW Pump Post Circulation
– This parameter is the amount of time the DHW pump will continue to run after a heat
demand has been satised or after a lock-out condition has occurred.
• System Pump Control
– This parameter provides the ability to set the system pump functionality to be:
Auto – the pump will turn on automatically upon a call for heat.
Alway s On – the pump will run continuously, with or without a heat demand.
O Du ring DHW – the pump will not turn on during a DHW heat demand.
Disable – the pump will not turn on during a call for heat.
• System Pump Post Circulation
– This parameter is the amount of time the System pump will continue to run after a
heat demand has been satised or after a lock-out condition has occurred.
• Vari-Prime -
Select Vari-Prime to get to the controls of the variable speed pump.
Vari-Prime is available only on hydronic units.
CONFIGURATION