Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 81
8.D.8 Temp Limits
To navigate to the Temp Limits Screen, touch the Temp Limits Icon on the Conguration Screen.
The Temp Limits Conguration Screen allows adjustment of the following parameters:
• Auto Reset CH– The temperature at which the unit will shut down when outlet temperature exceeds its maximum
auto reset set point. The control will automatically reset, based on the reset dierential.
• Manual Reset CH – The temperature at which the unit will shut down when outlet temperature exceeds its
maximum manual reset set point. The control will require manual reset in this condition.
•ResetDierential– The value below the Auto Reset temperature at which the unit will automatically reset itself and
resume functionality.
• Delta T Parameters– The MIN and MAX
Temperature between which your system
will modulate.
• Flue Limitation – Sets the ue temp
limitations.
• Outlet Limitation Parameters – Allows
for the adjustment of Min and Max Outlet
Temps.
8.D.7 Manual Firing Rate
To navigate to the Manual Firing Rate Screen, touch the Manual Firing Rate Icon on the Conguration Screen.
The Manual Firing Rate Control Screen allows the adjustment of the following parameters:
• Enable/Disable – Enables and disables the manual ring rate functionality.
• Fan Speed – With the manual ring rate functionality enabled, an operator can manually set the ring rate. This
functionality is used for combustion adjustment purposes. With the manual ring rate functionality enabled, and the
desired fan speed set, apply a call for heat at CH1/DHW1 and the boiler/heater will step through the ignition process
and run at the set fan speed.
• Time Out – is the setable amount of time that the operator has to adjust the Manual Firing Rate before the control
will go back to automatic. It’s a walkaway timer and safety feature.
CONFIGURATION