Installation / Operation Instruction Manual
Table Of Contents
- Brute MagnaTech
- Table of Contents. Page 1
- SECTION 1 General Information
- SECTION 2 Venting and Combustion Air
- SECTION 3 Gas supply and Piping
- SECTION 4 Water Flow and Headloss Data
- SECTION 5 Piping
- SECTION 6 Condensate Drain Trap
- SECTION 7 Electrical Connections
- SECTION 8 Control Operation
- 8.A The Home Screen
- 8.B Login to Lock / Unlock the Display Screen
- 8.C Quick Start
- 8.D Configuration
- 8.E Service Screens
- 8.F Messages and USB
- 8.G Active Demands
- SECTION 9 Parameter Tables
- SECTION 10 Initial startup Instructions
- SECTION 11 Maintenance
- SECTION 12 Troubleshooting
- SECTION 13 Replacement Parts
- 13.A General Information
- 13.B Component Illustrations, Parts Lists, and Part Numbers
- 13.B.1 Final Assembly, Part Numbers
- 13.B.2 Frame and Jacket Assembly, Part Numbers
- 13.B.3 Control Panel, Part Numbers
- 13.B.4 Air / Gas System, Part Numbers (Model 1600)
- 13.B.5 Air / Gas System, Part Numbers (Model 2000)
- 13.B.6 Air / Gas System, Part Numbers (Models 2500 & 3000)
- 13.B.7 Air / Gas System, Part Numbers(Models 3500 and 4000)
- 13.B.8 AC Distribution Box, Part Numbers (Model 1600)
- 13.B.9 AC Distribution Box, Part Numbers (Model 2000)
- 13.B.10 AC Distribution Box, Part Numbers (Models 2500 to 4000)
- 13.B.11 Inlet Waterway Assemblies, Part Numbers
- 13.B.12 Outlet Waterway Assemblies, Part Numbers
- 13.B.13 Gas Train Assembly, Part Numbers(Models 1600, 2000, 2500 and 3000)
- 13.B.14 Gas Train Assembly, Part Numbers (Models 3500 and 4000)
Page 84
Figure 41. External Setp Point Example
8.D.9.a External – Remote Set Point
External (0 – 10VDC or 4 – 20mA)
• An External heat demand can be initiated by a Building Automation System (BAS) using a 0-10VDC or 4-20mA
signal. This input can be congured for Remote Set Point or Remote Firing Rate operations.
• With Remote Set Point selected, the unit will initiate a heat demand once the analog input signal exceeds the
Demand On value. Once the demand is initiated, the analog input signal must be lower than Demand O to
remove the heat demand. With an active demand, the unit will locate the set point according to the analog input
signal.
• Using the default values for Boiler Max Set Point (180°F), Boiler Min Set Point (140°F), Demand Minimum
(2.5VDC), Demand Maximum (10.0VDC), the unit will linearize the set point, as shown in Figure 41.
CONFIGURATION