Installation / Operation Instruction Manual

Page 21
Brute Deluxe (200, 300, 400), Install & Operating
Table 8. Water Flow Requirements - BMT2V.
Model
(Size)
gpm ft Temp Rise °F lpm m Temp. Rise °C
S N H S N H S N H S N H S N H S N H
200 23 35 45 1.9 4.4 7.3 15 10 8 87 132 170 0.6 1.3 2.2 8 6 4
300 23 35 45 2.0 4.5 7.4 22 15 11 87 132 170 0.6 1.4 2.3 12 8 6
400 23 35 45 2.0 4.5 7.4 30 19 15 87 132 170 0.6 1.4 2.3 17 11 8
Notes:
1. S = soft water (1 to 7.5 grains hardness)
2. N = normal water (7.6 to 17 grains hardness)
3. H = hard water (more than 17 grains hardness)
4. gpm = gallons per minute, lpm = liters per minute, ft = head loss in feet, m = head loss in meters
5. Head loss is for heater's heat exchanger only