Brute Deluxe (200, 300, 400), Install & Operating
LEDs State Description
1. Power
2. Heat – On = call for heat; Flashes for Boiler
sensor error
3. DHW – On = call for DHW; Flashes for
outdoor sensor error
4. WWSD – On = Outdoor Reset AND WWSD
Active AND control in WWSD; Flashes for outdoor
sensor error, operation continues with xed boiler
target of 140°F.
When a call for HEAT and/or DHW is present the
pump contact (5A max) will be energized. Post purge
can be selected via dip switch #5, Pump Post Purge
Inactive (O) /Active 3 min. (On). In the On position
the pump will continue to run for 3 min after the last
call has been satised. When the dip switch is O
there is no post purge of the pump, the pump turns o
immediately after the last call is removed. Bradford
White strongly recommends using a pump post purge.
During WWSD and a call for HEAT is present the
pump will remain o.
Pump Exercising The control exercises the
boiler pump every 3 days of inactivity. While the
control is exercising the pump all LEDs will turn o
and the power LED will ash for 10 seconds.
Staging (where applicable – factory setting):
Dip switch #1 is used to select the number of stages:
2-Stage (O) / Single Stage (On).
For 2-stage operation, the rst stage is cycled
on Proportional error and the second stage is cycled
based on PI according to a xed algorithm. No user
adjustment is necessary.
Note: All stages are turned o when the water
outlet temperature reaches the Maximum setting
that is elected via dip switch #4, Boiler Maximum
210°F (O) / 190°F (On). Commercial boilers have
dip switch #2 set for ‘O’ to allow setpoint control.
Utilize dial to set desired outlet temp.
NOTE:
This boiler is equipped with a feature that saves
energy by reducing the boiler water temperature as
the heating load decreases. This feature is equipped
with an override which is provided primarily to permit
the use of an external energy management system
that serves the same function. THIS OVERRIDE
MUST NOT BE USED UNLESS AT LEAST ONE OF
THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is
installed that reduces the boiler water temperature
as the heating load decreases.
• This boiler is not used for any space heating.
• This boiler is part of a modular or multiple boiler
system having a total input of 300,000 BTU/hr or
greater.
• This boiler equipped with a tankless coil.
Auto Boiler Target Setpoint: Space Heating:
The boiler target temperature is automatically
determined from Space Heating and DHW
requirements. Space heating is based on outdoor reset.
When both a Heat Call and a DHW Call are present
at the same time, the control operates to provide the
higher boiler target temperature.
Heating Curve (Outdoor Temperature Reset)
The control uses a linear heating curve to calculate
a target setpoint. The following data are used
to calculate the target setpoint from the outdoor
temperature.
1. The heating curve or reset ratio (RR) is set by
the potentiometer with a range of 0.4 to 3.6.
2. The room temperature is xed at 70 deg F.
3. Boiler target = 70 deg F + RR x (70 deg F -
outdoor temp)
Outdoor Heating Curve=Reset Ratio (RR)=
Temp F 1.0 2.0 3.0
Boiler Target F
-30 170
210
210
-20 160
-10
150
0
10 190
20 170
30
150
190
40 160
50
130
60
70 WWSD OFF
Boiler Target Temperature Calculation:
Boiler Target = 70 deg F +RR x (70–Outdoor Temp)
Table 9. Boiler Target Temperature
DHW Operation The boiler target for DHW
calls is xed at 180 deg F.
Note: There is no control of a DHW pump, so the
boiler pump runs with the call for DHW.
Limiting The boiler target is limited to a
minimum and a maximum target to ensure that the
water temperature does not exceed the limits.
1. Target Min - The boiler target minimum is
the point at which the stages will start to turn on to
maintain a minimum water temperature. The Boiler
Minimum water temperature is 130 deg F, regardless
of other calculated targets. To ensure that the water
temperature is greater than the Boiler Minimum water
temperature the target is increased to allow the stages
to cycle on by the Boiler Minimum water temperature,