The minimum inlet water temperature for the
Brute Deluxe is 130°F (54°C) to avoid condensing on
the copper coils.
4.B.2 Hot Water Supply Piping —Water
Heater
Follow the tank manufacturers guidelines for
completion of the hot water system connections.
NOTE: A listed temperature and pressure relief
valve listed as complying with the Standard
for Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems (ANSI
Z21.22/CSA 4.4), of suitable discharge capacity
must be installed in the separate storage tank
system.
If the Brute Deluxe water heater is installed in
a closed water supply system, such as one having a
backow preventer in the cold water supply line, the
relief valve may discharge periodically, due to thermal
expansion. Means (such as a properly-sized expansion
tank) shall be provided to control thermal expansion.
Contact the water supplier or local plumbing inspector
on how to control this situation.
4.B.3 Water Flow Requirements —
Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
be deposited on the unit’s heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water
ow requirements for the Brute Deluxe water heater
are based upon the hardness of the water. The water
ow is kept high enough to prevent scaling, but low
enough to prevent tube erosion. For extremely soft or
hard water, cupro-nickel tubes are available. Contact a
Bradford White representative if you have questions or
concerns about water quality.
Pump-mounted water heaters can be ordered with
standard pumps for soft or normal water. The pumps
used are sized for the head loss through the heater, plus
30 feet (9.1m) of full-sized piping (same size as heater
outlet) and a normal number of ttings. For hard water
conditions (more than 17 grains per gallon), use a
non-pump-mounted heater with a properly-sized eld-
installed pump.
Table 8 species water ow rates for water
heaters, which will enable the user to size a pump. The
head loss shown is for the heater only, and the user
will need to add the head loss of the piping system to
properly size the pump.
4.B.4 Combined Water Heating (potable) and
Space Heating — Water Heater
NOTE: These systems are not allowed in the
Commonwealth of Massachusetts.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
water used for space heating.
This water heater when used to supply potable
water shall not be connected to any heating system
or component(s) previously used with a non-potable
water heating appliance.
When the system requires water for heating at
temperatures higher than required for other uses,
an anti-scald mixing or tempering valve shall be
installed to temper the water for those uses in order
to reduce scald hazard potential.
4.B.5 Freeze Protection — Water Heater
Although Brute Deluxe water heaters are design-
certied for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from ring. Any time a
heater is subjected to freezing conditions, and the
heater is not able to re, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or ooding conditions.
Contact the local factory representative or
Bradford White for additional information.