Submittal
Clearances
* Whenventand/orcombustionairconnectstotheback,recommendedclearance
is36"91cm.
** 1"whenb-ventisused.
Required Clearance from Suggested Service
Appliance Combustible Material Access Clearance
Surface inches cm inches cm
Left Side 1 2.5 24 61.0
RightSide 1 2.5 24 61.0
Top 1 2.5 12 30.5
Back* 1 2.5 12 30.5
Front 1 2.5 36 91.4
Vertical Vent**
(Category 1) 6 15.2
Horizontal Vent
(Category3) perUL1738ventingsystemsupplier'sinstructions
Recovery
Data
WATER TEMPERATURE RISE IN °F
40°F 50°F 60°F 70°F 80°F 90°F 100°F 120°F 140°F
Size GPH GPH GPH GPH GPH GPH GPH GPH GPH
200 510 408 340 291 255 227 204 170 146
300 765 612 510 437 383 340 306 255 219
400 1020 816 680 583 510 453 408 340 291
NOTE: GPH = gallons per hour.
WATER TEMPERATURE RISE IN °C
22°C 28°C 33°C 39°C 44°C 50°C 56°C 67°C 78°C
Size L/h L/h L/h L/h L/h L/h L/h L/h L/h
200 1928 1542 1285 1100 964 858 771 643 552
300 2892 2313 1928 1652 1448 1285 1157 964 828
400 3856 3084 2570 2204 1928 1712 1542 1285 1100
NOTE: L/h = Liters per hour.
Electrical
Data
MT2H&MT2V Boiler/HeaterCircuitSize PumpDelayConnectionRating Blower
(non-pump mounted)
Size Volts Phase Amps PilotDuty Phase Power
Included
200–400 120 Single 15 24V Single
Up to
in Boiler
25VA
Circuit
BMT2H & BMT2V