Installation / Operation Instruction Manual

8
Minimum Clearances
This installation shall allow access to the front of the water heater and
adequate clearance shall be provided for servicing and operating this water
heater. The water heater may be installed on either a combustible or non-
combustible floor. If the water heater is to be installed directly on carpeting, it
shall be installed on top of a metal or wood panel (or equivalent) extending
beyond the full width and depth of the appliance by at least 3 in (7.6 cm) in
any direction or, if the appliance is to be installed in an alcove or closet, the
entire floor shall be covered by the panel.
If the rating plate or the label on the front of the heater specifies
minimum clearances less than those listed in the below table, the water
heater may be installed in accordance with the minimum clearances
listed on the rating plate or the label on the front of the heater.
If it is necessary to install this water heater in an alcove, use the clearances
listed in Figure 1.
Figure 1
WARNING
Failure to adhere to these installation and operating instructions may
create a hazard to life and property and will nullify the warranty.