Control Circuit Sequence (continued)
Certain other control components are available as “Optional“. These controls are specified when the installation
has unique requirements that must be safeguarded. When these optional components are installed the control
circuit wiring diagram accordingly will include these components. The optional equipment available from the
manufacturer includes the following:
High Water Pressure Switch
Low Water Pressure Switch
Low Water Level Switch
Alarm Horn
Heating Element Sequencers
Electrical Door Lock
Control Circuit Sequence of
Operation with Optional Controls
Line voltage from
power circuit
Appropriate line
voltage multi-tap
terminal
Same as explained on page 10 with the following
exceptions:
-Hi and Low Pressure Switch and Low Water Level
Switch when specified are always wired in series
ahead of the high-limit control.
-Heating Element Sequencers are wired in series
with contactor coils staging contactor activation at
intervals of approximately 20 seconds.
-Alarm Horn is wired in series ahead of the
thermostat. It monitors only the High and Low
pressure switch, Low Water Level Switch and the
High-Limit (ECO). If either of these switches open,
power to the horn relay is interrupted causing the
relay to close, sounding the alarm horn.
-Electrical Door Lock is wired in parallel to secure the
access to the water heater control cabinet. This
device will lock the control cabinet door when the
120VAC control circuit voltage is applied. Once the
door is opened, the water heater can be re-
energized, if necessary, for service diagnosis.
Control Circuit Wire Diagram
Showing OpƟonal Controls