Installation / Operation Instruction Manual
Table Of Contents
- WITH TROUBLESHOOTING GUIDE
- Non-Flue Damper Models (Figure 2)
- Flue Damper Models and Non-Flue Damper Models (Figure 3)
- Non-Flue Damper Models (Figure 4)
- Front, sides and Rear “A”
- Input
- 2 in. (5.1 CM)
- Less than or equal to 300,000 BTUH
- 6 in (15.2 CM)
- Greater than 300,000 BTUH
- IMPORTANT-The flow of combustion and ventilating air must not be obstructed.
- MECHANICAL EXHAUSTING OF ROOM AIR - Where an exhaust fan is installed in the same room with this water heater and combustion air is drawn from inside the room, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE A...
29
To Change Temperature Format in Display from °F to °C or ˚C to ˚F:
Step 1: Press “SELECT” button until °F/°C is displayed.
Step 2: Press “SET” button to change temperature format. Symbol °F/°C will flash.
Step 3a: Press “Temperature Up” button to change temperature format to °C.
SELECT
SET
Status
°C
idle
Operational
Step 3a
°F/°C
°F/°C Flashes
Changes to "°C"
SELECT
SET
Status
idle
Operational
Press
select
Step 1
°F
°F/°C
SELECT
SET
Status
idle
Operational
Step 2
°F/°C Flashes
°F
°F/°C