Installation / Operation Instruction Manual
Table Of Contents
- WITH TROUBLESHOOTING GUIDE
- Non-Flue Damper Models (Figure 2)
- Flue Damper Models and Non-Flue Damper Models (Figure 3)
- Non-Flue Damper Models (Figure 4)
- Front, sides and Rear “A”
- Input
- 2 in. (5.1 CM)
- Less than or equal to 300,000 BTUH
- 6 in (15.2 CM)
- Greater than 300,000 BTUH
- IMPORTANT-The flow of combustion and ventilating air must not be obstructed.
- MECHANICAL EXHAUSTING OF ROOM AIR - Where an exhaust fan is installed in the same room with this water heater and combustion air is drawn from inside the room, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE A...
16
3. Secure the flue damper to the jacket top with sheet metal screws.
4. Connect the damper wiring plug to the damper wire harness connector on the side of the water heater. Note: The plug
and connector can only be engaged one way (polarized).
5. The Lighting and Operating instructions are outlined in this manual. The damper must be in the open position when
the water heater main burner is operating (the arrow on the damper plate is in the “up” position when open. Be certain
the arrow is in a visible position when installed).
DRAFT DIVERTER
This water heater has been shipped with a draft diverter for which it was designed. Remove the bag containing the legs
and instructions from the draft diverter. Attach the legs to the draft diverter and attach the draft diverter to the water heater
per the instructions in the bag.
Figure 6
Modification to the flue damper or the draft diverter may result in personal injury, property damage or death.
The flue damper and draft diverter are to be placed in position and operate exactly as stated in these
instructions without modification.
CAUTION