Installation / Operation Instruction Manual

10 2385032000B 9/15
TightenMetalClamparoundbodyofventpipe. Metalclampfastenstowallwithwoodscrews

HighEfficiencyCommercial CondensingModels:
Forhorizontalsectionsoffluepipe,thepipemustbeinstal ledwithaslightupwardslopeofapproximately¼inchper
foot(20mmpermeter)towardthewaterheatertoallowcondensatetodrainintothecondensateelbow.
ResidentialandCommercialPowerDirectVent/PowerVentModels:
Topreventcondensatefromaccumulatingintheexhaustblower,installthehorizontalventpipewithadownwardslope
towardtheventterminalof¼inchperfoot(20mmpermeter)ofhorizontalventpipe.Anoptionalcondensatekitis
availableforresidentialpowerventmodelsorateefittingwithacondensatedrainloopmaybeusedoncommercial
powerdirectventmodelstopreventcondensateaccumulationin
theblowerforlongverticalrunsofventpipe.Referto
theventingsectionoftheInstallationandOperatingInstructionssuppliedwiththewaterheater.
Step6:Ifanyofthestraightpipesectionsneedtobecut,useahacksawandmakeastraightcutonthemale
(ungasketed)endofthepipe.Whenmakingthecut,allowforthe2”minimum(51mm)insertiondistanceinsidethe
femaleendofthepipe.Makesurethecutsaremadesquareandusearazorknifetodeburrtheedgesofthecutpipeto
avoidanysharpedgesthat
maydamagethegasket.
DuraVenthasadjustableventpipesectionsavailable,whichallow4.5inches(114mm)ofadjustmenttothelength.
WARNING
Cut pipe edges must be properly deburred. Damage to the gasket from not deburring the edges of the cut male
end may result in the release of dangerous flue products.